LOW NOX MODELS 207A, 267A, 337A & 407A:
Make sure the power and gas are off.
1. Locate Lo Nox tab and P-10 air switch terminal on the board as shown in Fig. 17 and Fig. 18.
2. Break off tab shown in Fig. 19 with pliers.
3. Attach the wire from the air switch to the P-10 location shown in Fig. 20.
2151 Eastman Ave., Oxnard, CA 93030 805-278-5300 Fax 800-777-7026
www.raypak.com
Technical support is available M-F, 5:30 AM to 5:00 PM PST, at 800-947-2975 or 800-627-2975
BREAK
TAB
WIRE AIR
SWITCH
TO P-10
HERE
Fig. 18
Page 8
Fig. 17
P-10
TERMINAL
LO NOX
TAB
P–10 TERMINAL
Fig. 19
Fig. 20
BROKEN TAB
P/N 241169 Rev.-3
See also other documents in the category Raypak Water equipment:
- 902B (5 pages)
- Hi Delta 992B-1262B (66 pages)
- CHX (4 pages)
- R265B (7 pages)
- 406A (55 pages)
- 752B (8 pages)
- P-1223 (4 pages)
- RHP160 (2 pages)
- CR24-185 (8 pages)
- 206A (55 pages)
- 207 (4 pages)
- 6200.90 (1 page)
- Finned Water-Tube Pool Heaters 2072B-2342B (5 pages)
- P-4001 (38 pages)
- VERSA 105 (2 pages)
- MVB 504 (8 pages)
- RAYTHERM P-2100 (36 pages)
- CR406A (2 pages)
- RP2100 (52 pages)
- 402B (2 pages)
- 105A (4 pages)
- 2072B (7 pages)
- Versa 155 (2 pages)
- HI DELTA 2002B (3 pages)
- 538 To 4224 (18 pages)
- Versa 105B (32 pages)
- D-2 POWER VENT 206A (20 pages)
- Raytherm 514-824 (2 pages)
- Hi-Delta Commercial Swimming Pool Heater (1 page)
- 1802B-2342B (2 pages)
- C-R185B To P-R405B (52 pages)
- Commercial Cold Water Start (5 pages)
- 624 (2 pages)
- PS-4 PS-8 (32 pages)
- 407A (6 pages)
- 105B (31 pages)
- 155C (34 pages)
- R410A (2 pages)
- VERSA 155C (35 pages)
- HI DELTA 122-322 (44 pages)
- P (1 page)