beautypg.com

Raypak 503-2003 User Manual

Page 15

background image

15

Table F: Heater Rates of Flow and Pressure Drops

20°F T

30°F T

40°F T

Min. Flow

Max. Flow

Model

No.

gpm

P (ft)

gpm

P (ft)

gpm

P (ft)

gpm

P (ft)

T

gpm

P (ft)

T

503

44

2.8

29

1.4

N/A

N/A

25

1.1

35

100

11.3

9

753

65

6.4

44

3.1

33

1.9

33

1.9

40

100

13.8

13

1003

87

12.0

58

6.0

43

3.7

43

3.7

40

113

18.6

15

1252

109

20.9

73

10.2

54

6.2

54

6.2

40

113

22.2

19

1503

N/A

N/A

87

16.0

65

9.5

65

9.5

40

113

25.5

23

1753

N/A

N/A

102

22.5

76

13.4

76

13.4

40

113

27.2

27

2003

N/A

N/A

116

32.0

87

18.9

87

18.9

40

116

32.0

30

Notes: Basis for minimum flow is ΔT . Basis for maximum flow is gpm.

equipped with flow control valves or other automatic
means to prevent gravity circulation of the heater
water during the cooling cycle. It is highly recommend-
ed that the piping be insulated.

Air-Separation/Expansion Tank

All heaters should be equipped with a properly sized
expansion tank and air separator fitting as shown in
Fig. 9.

Three-Way Valves

Three-way valves intended to regulate system water
temperatures by reducing flow in the boiler should not
be used. Raypak heaters are high-recovery, low-mass
heaters which are not subject to thermal shock. See
Fig. 14 and instructions on page 17 for adjusting the
manual bypass.

Fig. 9: Air-Separation/Expansion Tank

*

Fig. 10: Single Heater - Low-Temperature (Heat Pump)

Application with Primary/Secondary Piping

*

Fig. 11: Dual Heaters (Reverse/Return)

with Primary/Secondary Piping

*Maximum 4 times the pipe diameter or 12”, whichever is less.

*Maximum 4 times the pipe diameter or 12”, whichever is less.