beautypg.com

Chapter 19 e-series specifications, Table 12. chloride e-series ups north america – Rackmount Solutions VA 10000 User Manual

Page 54

background image

50

Chloride Active and E-Series UPS User Manual

Chapter 19 E-Series Specifications

Table 12. Chloride E-Series UPS North America

UPS Model

E61XA

(E41XA*)

E101XA

(E81*)

E203XA

(E153XA*)

* Models may be upgraded to base kVA of UPS shown.

Electrical Data

Rating

6 kVA

10 kVA

20 kVA

Input

Voltage

208 VAC single-phase

208/120 three-
phase

Voltage range

170 V to 276 V

176 to 276 V

177 to 240 V

Frequency

50/60Hz ± 5%

Power factor (lambda)

>0.97

>0.95

Battery

Integrated battery type

Lead-calcium, maintenance-free

None

Battery voltage (V)

240

Runtimes (min.)
(half load/full load)

25/8

30/12

N/A

Runtimes (min.),1 battery cabinet
(half load/full load)

94/38

100/40

40/15

Output Voltage

Voltage - North American

120, 208, 240 VAC, single-phase

Voltage tolerance

± 3%

Frequency with mains control

see input frequency

Frequency with internal control

50/60 Hz, ± 0.5%

Distortion factor (linear/non-linear load)

max. 4%/max. 7%

max. 5%/ max.

8%

Permissible crest factor

3

Overload capability

130% for 2 sec., 110% for 10 sec.

output short-circuit proof

Common Data

Electrical safety

UL1778

Radio interference level

FCC Part 15 Class A

This manual is related to the following products: