Table 7. Minimum Requirements for E-Series UPS Installation

Term

ID

Description

E61 (E41)

E101 (E81)

E203 (E153)

Min.

Wire

Gaug

e

(awg)

Term

Torqu

e (in-

lbs)

Min.

Wire

Temp

. (°C)*

Min.

Wire

Gaug

e

(awg)

Term

Torqu

e (in-

lbs)

Min.

Wire

Temp

. (°C)*

Min.

Wire

Gaug

e

(awg)

Term

Torqu

e (in-

lbs)

Min.

Wire

Temp

.

(°C)*

GND

Chassis
Ground

**

40

75

**

45

75

**

45

90

L1/N

Line 1

8

40

75

6

45

75

4

45

90

L2

Line 2

8

40

75

6

45

75

4

45

90

L3

Line 3

N/A

N/A

N/A

N/A

N/A

N/A

4

45

90

120A

120 V from
Neutral

10

35

75

6

45

75

4

45

90

0

Neutral

10

35

75

6

45

75

4

45

90

88B

208 V from
120A

10

35

75

6

45

75

4

45

90

120B

120 V from
Neutral

10

35

75

6

45

75

4

45

90

GND

Chassis
Ground

opt

35

75

opt

45

75

opt

45

90

+

+240 VDC to -

N/A

N/A

N/A

4

45

75

4

45

75

-

Battery
Common

N/A

N/A

N/A

4

45

75

4

45

75

GND

Chassis
Ground

N/A

N/A

N/A

4

45

75

4

45

75

* Use insulated copper wire rated 75 C minimum.
** Must be no smaller than wire connected to L1/N and L2 (for E61 and E101) or L1, L2, L3 (for E203).

GND L1/N L2 120

0

88B 120 GND

208

120

120

LINE

OUT-

X3

X4

X2

X1

Chloride Active and E-Series UPS User Manual

35

Fig. 23: Wiring Diagram for the E61