Raypak 302-902 User Manual
Page 33

•
Horizontal Thru-wall Direct Vent Termination
The flue exhaust direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be installed in
a well or below grade. The direct vent cap must be installed at least one (1) foot above ground level and above normal snow
levels. The Raypak supplied flue exhaust direct vent cap must be utilized.
WARNING:
No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the
safety and health of inhabitants.
The Stainless Steel direct vent cap must be furnished by the boiler manufacturer in accordance with its
listing.
Use only the special gas vent pipes listed for use with category III gas burning heaters, such as the stainless steel Saf-T vent
by Heat Fab Inc. (413-744-2356). Pipe joints must be positively sealed. Follow carefully the vent manufacturers installation
instructions.
33
- 240692 (31 pages)
- HIDELTA 992B (68 pages)
- 1000 (74 pages)
- RAYTHERM 962-1826 (2 pages)
- 335 (1 page)
- 504-2004 (4 pages)
- 265 (14 pages)
- 751-1501 (2 pages)
- HI DELTA HD401 (48 pages)
- DEL TA LIMITED 899B (5 pages)
- 2100 - 4001 (2 pages)
- H-0042B (4 pages)
- 2005 (8 pages)
- HI DALTA HD401 (48 pages)
- XFYRE 400 (8 pages)
- 42 & 66 (2 pages)
- 992BE (5 pages)
- 500 (56 pages)
- 182-400 (2 pages)
- Gas Fired Boiler (8 pages)
- MVB 5042004 (56 pages)
- B0147 (43 pages)
- RAYTHERM 0042B (40 pages)
- WH 0090A (28 pages)
- H7 504-2004 (2 pages)
- 503-2003 (60 pages)
- XFYRE NINETY PLUS 850 (8 pages)
- XPAK 85 (68 pages)
- 0066B (38 pages)
- 195A (28 pages)
- Power Vent Raytherm 4001 (2 pages)
- FlexGas (1 page)
- XPAK 120 (12 pages)
- XTHERM 1505 (8 pages)
- RayTherm Commercial Boilers And Water Heater (4 pages)
- 0135B (6 pages)
- RayTemp Hot Water Energy Management Control (30 pages)
- 0090B (39 pages)
- B6000 (51 pages)
- B6000 (2 pages)
- 1001 (76 pages)
- RAYTHERM 133-4001 (44 pages)
- HI DELTA SS HD401 (4 pages)
- XFYRE 300-850 (2 pages)
- 30B (4 pages)