Operation Manual

GuardShield Safe 4

Figure 11: Adjustment with ILAS

5.2.6. Testing the protection field

After Installation and Alignment of the GuardShield

Safe 4 safety light curtain, the protection field has
to be tested with the test rod for the corresponding
resolution (14 or 30 mm) according Figure 12.

Figure 12: Correct testing of the protective field

using a test rod

5.3. Electrical Installation

5.3.1. Connection diagram

The transmitter and receiver are connected to the

machine control using a 5-wire cable.

For the transmitter and the receiver two M12 (for

cable - Ø 3 ... 6.5 mm) are supplied.

13

R

D

On optimal alignment of the light
curtain the ILAS light point can deflect
from the ILAS target point. The
maximum deflection adds up to the
following value due the operating
distance:

2 m

R = 7 mm

D = 7 mm

6 m

R = 20 mm

D = 21 mm

9 m

R = 30 mm

D = 32 mm

18 m R = 60 mm

D = 63 mm

30 m R = 99 mm

D = 105 mm

Transmitter

Receiver

Figure 13: Terminal block connection (see also

Figure 18)

Figure 14: M12/5 Pin connector

1) Operation with internal test
2) Test using a relay contact
3) Test using a PNP output

+24 VDC

0 V

1

2

3

4

Not connected

5

6

7

1)

3)

2)

Not connected

+24 VDC

0 V

1

2

3

5

4

6

7

R

L

R

L

OSSD 1

OSSD 2

Not connected

Not connected

Transmitter

Receiver

3

= 0 V

4

= Test 1

1

= + 24 VDC

2

= Test 2

Pin 5

= PE

Transmitter:

3

= 0 V

4

= OSSD 1

1

= + 24 VDC

2

= OSSD 2

5

= PE

Receiver:

Pin

Pin

Pin

Pin

Pin

Pin

Pin

Pin

Pin