National Instruments NI 9229 User Manual
Page 6

NI 9229/9239
6
ni.com
Caution
For Zone 2 applications, install a protection
device between the input signal and the NI 9229/9239
input terminal. The device must prevent the input
channel-to-COM voltage from exceeding 85 V if there is
a transient overvoltage condition.
Caution
For Zone 2 applications, connected signals must
be within the following limit:
Capacitance .......................... 0.01
μF max
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as Ex nA IIC T4 equipment
under DEMKO Certificate No. 07 ATEX 0626664X. Each module
is marked
II 3G and is suitable for use in Zone 2 hazardous
locations. If you are using the NI 9229/9239 in Gas
Group IIC hazardous locations or in ambient temperatures of
–40 °C
≤ Ta ≤ 70 °C, you must use the device in an NI chassis that
has been evaluated as EEx nC IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 equipment.