Scenario 1 – manual serial dial-in – N-Tron 102PC-SE User Manual
Page 33

(Revised 2010-11-15)
33
Scenario 1 – Manual Serial Dial-in
Login in to the Command prompt from the serial side.
Invoke # telnet
between the serial device and the remote server.
You can switch from Command Prompt to Dial-in session using restore session command.
You can switch from Dial-in session to Command Prompt using
Manual Dial-in Feature Through the Command Shell
Commands to Setup Manual Dial-In with the 102PC-SE
# set ip eth0 dhcp-client disable
# set ip eth0 ip-address 192.168.2.1
# set serial s0 baud-rate 115200
# set serial s0 data-bits 8
# set serial s0 parity none
# set serial s0 stop-bits 1
# set serial s0 flow-control rts-cts
# save
Once the above configuration is saved on the 102PC-SE, login to the 102PC-SE through the serial port. At the command shell invoke:
# telnet 192.168.2.10 23
The telnet client on board in the 102PC-SE establishes a virtual serial tunnel between the serial device and the Telnet Server.
Notes:
1.
You can not open more than one dial-in session.
2.
The dial-in session is closed when the telnet session is closed.
3.
When escape-monitor is enabled, care should be taken during file transfer that the escapemonitor-
ring is not part of the data.
4. The manual dial-in is supported for Telnet ONLY and not for UDP.