NI 9426 Operating Instructions and Specifications

4

ni.com

Ex nA IIC T4 hazardous locations; and nonhazardous locations
only. Follow these guidelines if you are installing the NI 9426 in a
potentially explosive environment. Not following these guidelines
may result in serious injury or death.

Caution

Do not disconnect I/O-side wires or connectors

unless power has been switched off or the area is known
to be nonhazardous.

Caution

Do not remove modules unless power has been

switched off or the area is known to be nonhazardous.

Caution

Substitution of components may impair

suitability for Class I, Division 2.

Caution

For Zone 2 applications, install the system

in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.

Caution

For Zone 2 applications, install a protection

device that prevents the V

sup

voltage from exceeding

42 V if there is a transient overvoltage condition.