PORT-A-COOL® Hazardous Location Units
*
Ill. MAINTENANCE & STORAGE
Very little maintenance is actually required on the PORT-A-COOL® unit. The primary topic which accounts
for most	of	the	maintenance	on	the	PORT-A-COOL® unit	is	cleanliness.	Keeping	the	PORT-A-COOL® unit	clean	will	
do	more	than	any	other	single	item	to	keep	your	new	PORT-A-COOL® unit	in	peak	operating	condition.	The	rug-
ged,	corrosion-resistant	construction	of	the	PORT-A-COOL® unit	and	industrial	grade	components	make	for	the	low	
maintenance	characteristics	of	the	PORT-A-COOL® unit.
A. Daily Maintenance
Daily maintenance is really more an operational consideration than actual maintenance. On a daily basis, the
pump	should	be	turned	off	approximately	l5	minutes	before	the	fan	is	turned	off.	This	will	allow	the	cooling	pads	
to	dry	out	and	help	extend	their	life,	helping	to	control	the	growth	of	algae,	mildew,	mold,	bacteria	and	other	odor-
causing	elements.
B. Weekly Maintenance
At the end of the week or at a scheduled time, the unit should be shut down and the sump tank should
be	drained.	This	is	accomplished	by	closing	the	Spray	Bar	Adjustment	Valve	and	opening	the	Drain	Valve.	If	it	is	
desired,	a	hose	may	be	attached	to	the	Drain	Valve	to	direct	the	drained	water	to	a	remote	disposal	area.	Once	the	
Drain	Valve	is	open,	starting	the	pump	will	drain	the	unit.
Once the sump is drained and the power disconnected, the pads may be removed to allow inspection of the
sump	tank.	Assuming that	the	PORT-A-COOL® unit		is	in	a	dusty	environment,	dust	will	be	collected	in	the	sump	
tank.	This	dirt	may	be	vacuumed	out	using	a	wet/dry	shop	vacuum	and	wiped	clean	with	a	cloth.
The inlet strainer should be removed, inspected and cleaned. It is located at the bottom end of the pump
siphon hose assembly.
C. Storage
Storage of the PORT-A-COOL® unit is very simple.
1) Drain all water from the sump tank and clean as instructed above, ensuring that the pads and
sump are completely dry.
2) Roll up the electrical power cord to insure that they will not be rolled over, tripped over or
caught in equipment.
3) Cover the
PORT-A-COOL® unit
completely to prevent dust build-up and store in a dry area. This also
helps prevent damage to the pads.