Table 8. Troubleshooting Guide (continued)
Alarm or Condition
Possible Cause
Action
1 beep
The UPS is running on
Correct the input voltage, if possible. The UPS
every 2
battery power because the
continues to operate on battery until the condition is
seconds
input voltage is too high or
corrected or the battery is completely discharged.
too low.
If the condition persists, the input voltage in your area
may differ from the UPS nominal.
1 beep per
Power requirements exceed
The UPS will automatically shut down in 3 minutes.
second
UPS capacity (overload is
Save your work immediately and turn off your
greater than 120%) or the
equipment. Turn off the UPS.
load is defective.
Remove some of the equipment from your UPS. You.
may need to obtain a larger capacity UPS.
1 beep per
The UPS is on battery and
Shutdown is imminent (30 seconds). Save your work
second
the power requirements
and turn off your equipment. Turn off the UPS.
exceed UPS capacity
Remove some of the equipment from the UPS. You
(overload is greater than
may need to obtain a larger capacity UPS.
120%) or the load is
defective.
Continuous
Battery test failed.
Check the battery connections and be sure the
beep
battery is fully charged.
If the
indicator still flashes, see “UPS
Maintenance” on page 15 to replace the battery. Call
your service representative if the problem persists
Continuous
UPS internal temperature is
Shutdown is imminent. Save your work and turn off
beep
too high.
your equipment. Turn off the UPS.
Clear vents and remove any heat sources. Wait at
least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.
Continuous
UPS fan fault (750-1400VA
Save your work and turn off your equipment. Turn off
beep
models only)
the UPS. Contact your service representative.