Powerware 5115A USB User Manual
Page 29

23
Powerware
®
5115A USB User’s Guide
•
www.powerware.com.au
Table 6. Battery
Configuration
500VA: (1) 12V, 9 Ah internal battery
750VA: (2) 12V, 7 or 7.2 Ah internal batteries
1000VA: (2) 12V, 9 Ah internal batteries
1400VA: (3) 12V, 9 Ah internal batteries
Voltage
500VA: 12 Vdc
750-1000VA: 24 Vdc
1400VA: 36 Vdc
Type
Sealed, maintenance free, valve regulated, lead acid
Charging
Advanced charging for faster recovery; less than 3 hours to
90% usable capacity at nominal line and no supplementary
power supply load
Monitoring
Advanced monitoring for earlier failure detection and warning
Table 7. Battery Run Times (in Minutes)
UPS Models by VA Ratings
Load (VA)
Watts
500
750
1000
1400
200
128
17
38
41
58
300
192
11
27
28
41
500
320
5
14
15
28
600
402
-
9
10
19
750
503
-
6
8
14
900
603
-
-
6
10
1000
670
-
-
5
8
1200
804
-
-
-
6
1400
938
-
-
-
5
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.