beautypg.com

Powerware 9125 Two-in-One UPS 2500 User Manual

Page 71

background image

TROUBLESHOOTING

EATON Powerware

®

9125 Two-in-One UPS (2500/3000 VA) User’s Guide

S 164201374 Rev D

www.powerware.com

65

Action

Possible Cause

Alarm or Condition

Shutdown - Low Battery

Shutdown imminent.

Prepare equipment for shutdown.

Bypass

The UPS is in Bypass mode.

The equipment is transferred to utility power; however,
the utility power continues to be passively filtered by the
UPS. Check for one of the following alarms:
Overtemperature, Overload, UPS Failure, or Battery
Service.

Bypass

Bypass is not available. Input
voltage is not within ±12% of
nominal or input frequency is not
within ±3% of nominal.

The UPS is receiving utility power that may be unstable
or in brownout conditions. The UPS continues to supply
power to your equipment. If conditions worsen, the UPS
may switch to battery power.

Battery Service

The batteries may be fully
discharged.

Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the batteries.
After charging the batteries, press and hold the
button for 3 seconds; then check the

indicator.

If the

indicator is still flashing, see “Replacing

Batteries” on page 52.

The batteries are not connected
correctly.

Check the battery connections. Call your service
representative if the problem persists.

Site Wiring Fault
(120V models only)

Ground wire connection does
not exist or the line and neutral
wires are reversed in the wall
outlet.

Have a qualified electrician correct the wiring.
To disable this alarm, see “Configuration Mode” on
page 41.

Overtemperature

The UPS internal temperature is
too high. The UPS transfers to
Bypass mode, allowing the UPS
to cool.

Turn off the UPS. Unplug or remove utility power from
the UPS. Clear vents and remove any heat sources.
Ensure the airflow around the UPS is not restricted. Wait
at least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.

Overload

Continuous audible
alarm

Power requirements exceed
UPS capacity (101–150% for
30 seconds) or the load is
defective.

Turn off the UPS. Unplug or remove utility power from
the UPS. Remove some of the equipment from the UPS.
Wait at least 5 seconds until all indicators are off and
restart the UPS.
If the overload condition persists (101–110% for
2 minutes or 111–150% for 30 seconds), the UPS
automatically shuts down.