beautypg.com

Maxim – PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEM User Manual

Page 10

background image

PV500-17 05-2000

Section 17

10

MAXIM

AXIAL FLOW GAS BURNER START-UP (continued)

17. Check flue gases with a flue analyzer to make

final settings of the air shutter.

a. The readings need to be taken from a

hole in the vent several inches above the
heater vent connection, but before draft
regulator.


b. Insert draft gauge into the 1/4" test

opening in the stack. Draft in stack should
read -.02" to -.06" W.C. Adjust draft
regulator, if installed.


c. When water in the tank is above 120? F,

insert analyzer or O

2

tester in 1/4" test

opening and take O

2

reading in

percentage.


d. Gradually close air shutter, taking O

2

reading at each adjustment of air shutter
until optimum O

2

% (4-6%) is reached. If

O

2

% decreases, open air shutter to last

reading where the greatest reading is
achieved.


e. Insert CO tester in 1/4" test opening and

take CO reading. CO should not exceed
.03%. A reading greater than .03%
indicates lack of air. Open air shutter
slightly and take readings until CO is
within proper range. Optimum reading is
no CO.


f. If air shutter was changed during CO test,

take a final O

2

reading.


g. Insert CO

2

tester in 1/4" test opening;

record in percentage.


h. Insert stack temperature gauge in 1/4"

test opening and read gross stack
temperature; maximum gross stack is to
be 450°F, minimum net stack is to be
300°F. (NOTE: net temperature is the
total stack temperature, less room
temperature.)
If an excessively high
gross stack temperature is recorded,
check the flue tubes for turbulators.

i. Make sure the air shutter is locked

securely in place.

18. On burners with pilots, recheck pilot to

make sure its operation has not
deteriorated if adjustments are made to the
air shutter. To do this, shut off the main
valve, check the flame response signal by
cycling the burner through several lightoffs.

19. Check each operating and limit control to

be sure they function properly by lowering
and raising the temperature setting on
each control, causing the burner to cycle
on and off.


NOTE: During the initial firing of the burner,

smoke that is not related to the burner
will be emitted from the heater. This is
normal during "burn in" and could
possibly continue for several hours.

20. Record the following information for future

use:

A. Air shutter position________________

B. Manifold gas pressure________"W.C.

C. Stack draft_________________"W.C.

D. O

2

reading_______________%(4-6%)

E. CO

2

reading______________%(8-9%)

F. CO reading________%(less than .03%)

G. Stack temperature:

Gross _______________________°F.

Less ambient__________________°F.

Net__________________________°F.

H. Combustion efficiency___________%