PVI Industries PV 6804 User Manual
Specification for domestic water heaters
SPECIFICATION FOR DOMESTIC WATER HEATERS
Condensing, Firetube, Gas-Fired Water Heaters with Polymer-Lined Storage Tanks
PV 6804 8/07
1
Furnish and install a PLATINUM condensing firetube gas water heater(s) as manufactured by PVI Industries, LLC
of Fort Worth, Texas. Supply quantities and model numbers as indicated on the plumbing schedule.
Gas and Electrical Consumption
The water heater will operate at 95% thermal efficiency when tested to ANSI Z21.10.3/CSA 4.3. The water heater
will comply with the thermal efficiency, standby loss, and all other requirements of ASHRAE 90.1-2001.
Pressure Vessel and Heating Surfaces
The water heater will be constructed and stamped in accordance with Section IV, Part HLW of the ASME code.
The storage section and heat exchanger of the water heater will be National Board Registered for a working
pressure of 160 psi.
The heat exchanger will be a firetube design with the combustion chamber and all heating surfaces completely
water-backed. The fireside of the combustion chamber will be of boiler-grade steel. The waterside of the combustion
chamber will be non-ferrous and sealed with PTFE polymer. The fire tubes will be solid copper. The heating surfaces will
be removable by unbolting from the pressure vessel, allowing 100% access to waterside surfaces. Heat exchanger
removal will provide a manway sized opening, allowing access to 100% of interior surfaces. All tank connection fittings
will be nonferrous and removable from the tank.
Tank Lining
The
entire lining will be applied after the tank is completely fabricated and all welding is completed. Lining will be a
thermoplastic polymer that is NSF 61 approved and consist of FDA compliant materials. Lining will consist of multiple
applications creating a continuous and nonporous barrier with no interruptions or discontinuities; including the tank-to-
fitting transitions. Lining will be confirmed to be 100% void-free by the ASTM D-5162 wet electrode standard. Testing
will occur only after complete pressure vessel fabrication with all welding completed. Lining will have a dielectric
resistance of 1600 volts per mil.
The lined tank will not require anode rods or electronic anodes and none will be used.
Burner and Venting
Combustion will be provided by a pre-mix, fan-assisted, ported stainless steel burner. The gas train will meet the
requirements of UL, FM and IRI for water heaters with a maximum input of 399,000 Btu/h.
Water heater will be a category IV, condensing, positive pressure appliance and UL approved for PVC venting
material. Water heater will vent through-the-wall unassisted for 100 equivalent feet through four-inch diameter pipe.
Appliance will simultaneously be able to accept direct inlet combustion air through up to 100 equivalent feet of four-inch
diameter material.
(continued)