beautypg.com

Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page 57

background image

PARAMETER

DESCRIPTION

FACTORY

SETTING

Part Number

Describes part number of actuator model

Per Drawing

Actuator Type

Describes type of actuator

Stand Alone

Command Source

Sets type of command signal

Analog

Home Controls

the

direction the actuator will

move, extending or retracting, to find the
mechanical stop (HOME)

Extend

Span

Sets the maximum stroke length,
measured from the HOME position

1.0 inches

Stop Position

Sets the signal loss position, measured
from the HOME position

0.0 inches

Interpolation Table

Sets how Demand signal is interpolated
between defined points

Linear

Position Loop Constant

63

Current Loop PID Constants

Proportional

2.0

Integral

200

Derivative

0

Velocity Loop PID Constants

Proportional

30

Integral

3,000

Derivative

0

Maximum Velocity

Sets the maximum velocity

10 in/s

Maximum Force

Sets the maximum force output

1267 lbf

Maximum Homing Velocity

Sets the maximum velocity used to find
the HOME position

0.5 in/s

Maximum Homing Force

Sets the maximum force the HFG2.0 will
use to find the HOME position

500 lbf

Maximum Holding Force

Sets the maximum force to be used to
hold at the HOME position while the
position demand is < 4.1mA and > 2mA

500 lbf

Table 3-5. Typical HFG2.0 Setup Parameters With Default Values

CH. 3: OPERATING THE HFG2.0

51