Table 3-1. default configuration for fault alarm – Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page 53

background image

Fault Type

Low

Alarm

High

Alarm

Fault

Enable

Persist

Time

Auto

Reset

Output

Driver Overcurrent

N/A

1000 lbf

Yes

10 Sec

Yes

Yes

Tracking Error

N/A

3.33 %

Yes

10 Sec

Yes

Yes

Position Demand

3.5 mA

20.5 mA

No

1 Sec

No

No

RDC

Failure N/A N/A Yes N/A No

Yes

+14 Volts

12.0 Volts

16.0 Volts

Yes

7.5 Sec

Yes

Yes

–14 Volts

–16.0 Volts

–12.0 Volts

Yes 7.5

Sec Yes Yes

Input Voltage

75.0 Volts

180.0 Volts

Yes

7.5 Sec

Yes

Yes

EEPROM

Checksum

N/A N/A Yes N/A No

Yes

Motor High Temp

N/A

130° C

No

10 Sec

No

No

Electronics High Temp

N/A

110° C

Yes

10 Sec

Yes

Yes

+5 Volts

4.5 Volts

5.5 Volts

Yes

7.5 Sec

Yes

Yes

Watchdog

Expired N/A N/A Yes N/A No

Yes

EEPROM

Write N/A N/A Yes N/A No

Yes

Table 3-1. Default Configuration For FAULT Alarm

Fault Type

Low

Alarm

High

Alarm

Fault

Enable

Persist

Time

Shut-

Down

Output

Driver Overcurrent

N/A

1000 lbf

No

10 Sec

No

No

Tracking Error

N/A

3.33 %

No

10 Sec

No

No

Position Demand

2 mA

22 mA

No

1 Sec

No

No

RDC

Failure N/A N/A No N/A No

No

+14 Volts

12.0 Volts

16.0 Volts No 7.5

Sec No No

–14 Volts

–16.0 Volts

–12.0 Volts No 7.5

Sec No No

Input Voltage

75.0 Volts

180.0 Volts

No

7.5 Sec

No

No

EEPROM Checksum

N/A

N/A

No

7.5 Sec

No

No

Motor High Temp

N/A

135° C

Yes

10 Sec

Yes

Yes

Electronics High Temp

N/A

110° C

No

10 Sec

No

No

+5 Volts

4.0 Volts

6.0 Volts

No

7.5 Sec

No

No

Watchdog

Expired N/A N/A No N/A No

No

EEPROM

Write N/A N/A No N/A No

No

Table 3-2. Default Configuration For OVERTEMP Alarm

CH. 3: OPERATING THE HFG2.0