Ct disconnection detection, Low frequency protection control 1, Low frequency protection control 2 – Panasonic CS-E21CKE User Manual
Page 34: Minimum frequency protection control

8.2.1.7. CT Disconnection Detection
1. Control Starting Condition
a. Total Current is below 0.74 ~ 0.94 Amp.
b. Operating Frequency is 72 Hz (E18CK), 95 Hz (E21CK) +1 and above.
c.
Continuously for 20s.
2. Control Contents
a. Abnormal signal transmitted to indoor unit after 3 minutes outdoor power is supplied. (Indoor unit stop)
3. Control Cancellation Condition
Starting condition, (1) is not fulfilled.
8.2.1.8. Low Frequency Protection Control 1
When the compressor operate at frequency lower than 22 Hz for 240 minutes, the operation frequency will be increased to 22 Hz
for two minutes.
8.2.1.9. Low Frequency Protection Control 2
When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T
15 or T
30
T
14 or T
28
Outdoor air (°C)
T
13 or T
38
T
4 or T
24
Indoor heat exchanger (°C)
T
30
T
0
8.2.1.10. Minimum Frequency Protection Control
• During cooling operation (Anti Freezing control, soft dry) carry out the following operation.
1. During remote control setting is less than 28 deg
Indoor Fan Speed
Above Hi
minHz =
21
Above Me-
minHz =
21
Less than Me-
minHz =
18
Auto
minHz =
16
2. During Powerful ON
minHz =
22
However, when less than thermo OFF for 120 sec. continuously, the above control will be cancel.
• During heating operation, operate the followings control.
1. During Remote Control setting is less than 18 deg
Indoor Fan Speed
Above Hi
minHz =
30
Above Lo
minHz =
25
Less than Lo
minHz =
15
2. During Powerful ON
minHz =
35
However, when less than thermo OFF for 100 sec. continuously, the above control will be cancel.
34