Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2
and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on
the above operation mode chart, every 30 minutes.
Remote Control Setting Temperature (°C)
T1
T2
T3
16 ~ 18
+10
+8
-5
19 ~ 22
+8
+7
-7
23 ~ 26
+7
+6
-7
27 ~ 30
+6
+5
-8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from
Temperature shifts (°C)
Cooling/Soft Dry
→ Heating
-2
Heating
→ Cooling/Soft Dry
+2
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
8.1.7. Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
• Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)
[Cooling, Dry, Fan]
Remote Control
—
O
O
O
O
O
—
—
—
Tab (rpm)
SHI
Hi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E18CK
1530
1440
1360
1290
1220
1150
850
760
630
E21CK
1610
1520
1420
1330
1240
1150
890
800
630
[Heating]
Remote Control
—
O
O
O
O
O
—
—
—
Tab (rpm)
SSHI
SHi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E18CK
1590
1560
1480
1410
1340
1270
850
400
300
E21CK
1640
1610
1520
1440
1350
1270
890
400
300
19