PV 413 8/05 817-335-9531 ● 800-433-5654 ● FAX 800-880-2019 ● www.pvi.com


Model Number: Serial Number:

VENTING and COMBUSTION AIR

Vent Material: (CPVC – Water Heaters Only; AL29-4C Stainless Steel – Boilers or Water Heaters)

Vent Diameter:

inches; Vent Length: feet Vent Type:

Through-the-roof

Through Sidewall

Does vent have condensate drain?

Yes

No Does vent have elbows?

Yes; Qty

No

Does vent contain any of these devices?

Power Vent

Draft Inducer

Draft Regulator

Flue Damper

Combustion air louvers or openings?

Yes; Qty: Size:

No Interlocked?

Yes

No

Have direct-ducted combustion air?

Yes; duct diameter

inches, length

feet.

No

Duct Material: Does duct have elbows?

Yes; Qty

No

GAS SUPPLY

Type of Gas:

Natural

LP

Inlet Static Gas Pressure:

“W.C. (14”W.C. maximum)

Gas Supply Pipe Size:

Inlet Flow Gas Pressure:

“W.C. (see data label)

Combination Gas Pressure Switch Setting: High

“W.C. Low “W.C.

COMBUSTION ANALYSIS

Boilers

Heaters

1

st

Stage

2

nd

Stage

Pilot Gas Pressure

Manifold Gas Pressure

Carbon Dioxide CO

2

(8-9%)

Oxygen O

2

(5-7%)

Carbon Monoxide CO (less than 200 ppm)

Nitrogen Oxide NO

X

(if available)

Vent Pressure (+.25” to + 2.0” W.C.)

Gross Vent Temperature (maximum 230°F)

less Room Temperature °F

= Net Vent Temperature °F

Important: You must submit the original copy of the completed form to your PVI representative before the
warranty will become effective on this product. Contact Customer Service for assistance at 1-800-433-5654.

Service Company Name:

Phone:

Service Co. Address:

Start-up Performed By:

Date:

Customer: Phone No.: Date: