Nternal, Ypass, Witch – Powerware Ferrups FE/QFE 500VA User Manual
Page 51: Nstallation

45
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
:
Rev A www.powerware.com
C H A P T E R
6
I
NTERNAL
B
YPASS
S
WITCH
I
NSTALLATION
W A R N I N G
Only qualified service personnel (such as a licensed electrician) should perform the
hardwired installation. Risk of electrical shock.
C A U T I O N
Before you install the bypass switch, verify that the bypass switch and the AC
disconnect switch are in the OFF position.
1. Identify the installation wiring diagram that applies to your
FERRUPS (see Table 21).
Table 21. Internal Bypass Switch Wiring Diagrams
Model (Frequency)
UPS Input Voltage
UPS Output Voltage
Bypass Switch Type
Wiring Diagram
FE 4.3–18 kVA (60 Hz)
120
(4.3–7 kVA only)
120
MBB or BBM
Figure 17 on page 49
208 or 240
120/208 or 120/240
MBB or BBM
For 208V, use BBM only
Figure 18 on page 50
208 or 480 source*/
240 input
120/240
MBB or BBM
Figure 19 on page 51
220**
220
BBM
Figure 20 on page 52
QFE 4.3–18 kVA (50 Hz)
220, 230, or 240
220, 230, or 240
MBB or BBM
Figure 20 on page 52
*With a step-up or step-down transformer.
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,
or (b) split-phase installations that require 220 Vac.