Powerware Ferrups FE/QFE 500VA User Manual
Page 36

External Bypass Switch Installation
30
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide
:
Rev A www.powerware.com
Wiring Diagram
Bypass Switch Type
UPS Output Voltage
UPS Input Voltage
Model (Frequency)
FE 4.3–18 kVA (60 Hz)
120
(4.3–7 kVA only)
120
MBB or BBM
Figure 12 on page 40
208 or 240
120/208 or 120/240
MBB or BBM
For 208V, use BBM only
Figure 13 on page 41
208 or 480 source*/
240 input
120/240
MBB or BBM
Figure 14 on page 42
220**
220
BBM
Figure 15 on page 43
QFE 4.3–18 kVA (50 Hz)
220, 230, or 240
220, 230, or 240
MBB or BBM
Figure 15 on page 43
*With a step-up or step-down transformer.
**Contact your service representative for (a) single-phase installations that do not have the same input and output voltage,
or (b) split-phase installations that require 220 Vac.