Patterson-Kelley MOD-04 User Manual
Page 32

Modu-Fire
®
Gas-Fired Boiler
Maintenance
29
minal 9 of the Combustion Control is energized. 
This opens the main gas valve and energizes the 
air gas ratio control. The 15 second "Main 
Flame Establishing” period begins. If pilot 
flame has not been established, the unit will 
lock out on pilot flame failure. 
13. After the 15 second “Main Flame Establishing
Period” if flame has been established, Terminal 
8 of the combustion control is de-energized, 
closing the pilot valve. Terminal 15 is ener-
gized, providing power to the modulating con-
trol of the boiler. If main flame has not been es-
tablished, the unit will lock out on main flame 
failure. 
14. The unit modulates between the low fire setting
and the high fire setting to maintain the desired 
outlet water temp set point. 
15. When the load is below the low fire rating of the
boiler the boiler will continue firing and the out-
let water temperature will rise until it reaches 
operating limit setpoint value. At this point the 
operating control switch opens and the combus-
tion control is de-energized at Terminal 6 and 
the indicator for HEAT is turned off. This ac-
tion also de-energizes Terminal 9 thus closing 
the main gas valve and the air gas ratio control 
valve. Terminal 14 is energized which applies 
power to the close terminal of the air damper 
motor. The air damper closes. 
16. When the water temperature is reduced by the
load on the system, the operating control switch 
will close again. The operating sequence will 
recycle to step 5, provided the limits on water 
flow, gas pressure and high temperature are all 
met. 
5.6
T
ROUBLESHOOTING
Loss of Power
In the event of loss of power, the entire boiler sys-
tem is de-energized, closing all automatic valves 
and halting all boiler operations. When power is 
restored the sequence of operation will resume at 
Step 5, provided that all the limits are satisfied. 
Loss of Water Flow
When the "Water Flow" indicator is illuminated, 
there is insufficient water flow to close the switch, 
and burner operation is interrupted. When water 
flow is re-established, the sequence returns to Step 
2, provided that the other limits are satisfied. 
Gas Pressure
When the "Gas Press" indicator is illuminated, there 
has been either insufficient gas pressure or the gas 
pressure to the manifold is too high for safe and 
proper operation of the boiler. The power to the 
programmer will be interrupted. 
If a gas-supply shut-off valve is closed for any rea-
son, a low gas condition will result. 
When gas pressure is restored, the "Gas Press" indi-
cator will remain on and the boiler will remain 
locked out until the gas pressure switch is manually 
reset. 
In the event of a high gas manifold pressure condi-
tion, the “Gas Press” indicator will illuminate indi-
cating a potential air gas ratio control failure. This 
must be corrected by factory-trained personnel be-
fore restarting the boiler. 
Once the switch is reset, the sequence returns to 
Step 3, provided that the other limits are satisfied. 
High Water Temperature
When the boiler water has exceeded both the operat-
ing and high-limit temperature, power to the pro-
grammer is interrupted. When the water tempera-
ture falls below the high-limit temperature, the 
boiler will remain locked out until the switch is 
manually reset. Once the switch is reset, the se-
quence returns to Step 4 to await heat demand pro-
vided that the other limits are satisfied. 
Low Air
If the "Low Air" indicator remains on for longer 
than 20 seconds, there is insufficient airflow through 
the burner. An extended low air indication does not 
mean that the low air switch is defective. 
