beautypg.com

Patterson-Kelley MOD-04 User Manual

Page 26

background image

Modu-Fire

®

Gas-Fired Boiler

Operation

23

4. Turn power switch on. If a red warning indica-

tor is illuminated, see call for factory-trained
personnel to troubleshoot the problem and im-
plement corrective action. Wait five minutes
before attempting to reset boiler.

4.2.2 Normal Shut Down Procedures

1. Close all manual gas valves.

2. Turn off electric power.

4.2.3 Emergency Shut Off

Main and pilot gas cocks should be closed immedi-
ately if an emergency situation occurs; see Section
4.2.1 for the location of the gas cocks.

If overheating occurs or the gas supply fails to shut
off, do not turn off or disconnect the electrical sup-

ply to the pump. Instead, shut off the gas supply at
a location external to the boiler.

4.3

T

YPICAL

B

OILER

O

PERATING

C

ONDITIONS

Natural Gas

(1030 Btu/cu. Ft.)

Model

No.

Input

Rating

(Btu/hr)

Gas

Rate

(CFH)

Output

Capacity

(Btu/Hr.)

1000 1,000,000 971 850,000

1500 1,500,000 1,456 1,275,000

2000 2,000,000 1,942 1,700,000