Rs232 communications protocol & command set – Panamax M1500-UPS User Manual
Page 18
16
USA & Canada (800) 472-5555 • (707) 283-5900 • Fax (707) 283-5901
RS232 Communications Protocol & Command Set
(continued)
Condition
CL Outlet Bank switches ON
CL Outlet Bank switches OFF
NCL Outlet Bank switches ON
NCL Outlet Bank switches OFF
Response from UPS
CL_OUTLETS_ON
CL_OUTLETS_OFF
NCL_OUTLETS_ON
NCL_OUTLETS _OFF
Responses and Warning Messages
A warning message is to be transmitted whenever the status of the fol-
lowing systems changes:
Outlet Bank Status Messages
Whenever an outlet bank switches state (ON or OFF) the UPS sends a
message to the controller:
Condition
UPS is not in AVR or BATTERY
mode
UPS is in AVR boosting 13%
UPS is in AVR boosting 26%
UPS is in AVR bucking 15%
UPS is in BATTERY mode
Battery charge falls below critical
load threshold
Input voltage exceeds high volt-
age failure t’hold
Input voltage falls below low
voltage failure t’hold
Battery charge falls below critical
load threshold
Response from UPS
NORMAL
AVRBOOST1
AVRBOOST2
AVRBUCK1
BATTERY
LOWBATT
OVERVOLTAGE
UNDERVOLTAGE
LOWBATT
Power Status Messages
Whenever the power changes state the UPS sends a message to the
controller:
Invalid Command or Query
If the UPS receives a command or query ASCII string that it does not
understand, an error message is transmitted.
Condition:
Command or query not recognized or
properly formatted
Response from UPS:
INVALIDCMD