Rs232 communications protocol & command set, Continued) – Panamax M1500-UPS User Manual
Page 17
15
USA & Canada (800) 472-5555 • (707) 283-5900 • Fax (707) 283-5901
RS232 Communications Protocol & Command Set
(continued)
Request Input Voltage Level
Transmit the input AC voltage status
Send to UPS:
?INPUTVOLTS
Response from UPS:
XXX
XXX is the input AC voltage represented
in ASCII.
Request Output Voltage Status
Transmit the output voltage state
Send to UPS:
?OUTPUTSTAT
Response from UPS:
XXX
XXX is the output voltage represented
in ASCII.
If the UPS is not in AVR or BATTERY mode:
Response from UPS:
NORMAL
If the UPS is in AVR mode and boosting voltage by 13%
Response from UPS:
AVRBOOST1
If the UPS is in AVR mode and boosting voltage by 26%
Response from UPS:
AVRBOOST2
If the UPS is in AVR mode and bucking voltage by 11%
Response from UPS:
AVRBUCK1
If the UPS is in BATTERY mode
Response from UPS:
BATTERY
Request Load Level Status
Transmit the load level percentage.
Send to UPS:
?LOADSTAT
Response from UPS:
XX
XX is the load percentage represented
in ASCII.
Request Battery Charge Level Status
Transmit the remaining battery charge percentage.
Send to UPS:
?BATTERYSTAT
Response from UPS:
XX
XX is the battery charge percentage
represented in ASCII.
Identify Equipment
Transmit the model number, firmware number and revision.
Send to UPS:
?ID
Response from UPS:
PANAMAX
M1500-UPS
FW
REV
List all Commands and Queries
Send to UPS:
HELP
Response from UPS:
MAIN_ON
MAIN_OFF
NCL_ON
NCL_OFF
BATTHRESH
BEEPON
BEEPOFF
RESTORE
?OUTLETSTAT
?INPUTVOLTS
?OUTPUTSTAT
?LOADSTAT
?BATTERYSTAT
?ID
HELP