PV 17 8/05 817-335-9531 ● 800-433-5654 ● FAX 800-880-2019 ● www.pvi.com



Model Number: Serial Number:

GAS SUPPLY

Type of gas:

Natural

LP Gas Supply Pipe Size:

inches

Inlet Static Gas Pressure: “W.C. (14” W.C. maximum)

Inlet Flow Gas Pressure: “W.C. (see data label)

Combination Gas Pressure Switch Setting: High / Low “W.C.

COMBUSTION ANALYSIS

BURNER MODEL NO.: BURNER SERIAL NO.:

(For fixed rate burner, use High Fire column)

Low Fire

Mid Fire

High Fire

Pilot Gas Pressure

Manifold Gas Pressure

Carbon Dioxide CO

2

(8-9%)

Oxygen O

2

(5-7%)

Carbon Monoxide CO (less than 200 ppm)

Nitrogen Oxide NO

X

(if available)

Vent Pressure (-.02” to -.06” W.C.)

Gross Vent Temperature °F

less Room Temperature °F

= Net Vent Temperature °F

Important: You must submit the original copy of the completed form to your PVI representative before the
warranty will become effective on this product. Contact Customer Service for assistance at 1-800-433-5654.

Comments:

Service Company Name:

Phone:

Service Company Address:

Start-up Performed By:

Date:

Customer Representative:

Date: