POWERWARE 9 BATTERY BACKUP TIMES (in minutes)

Internal

Internal

UPS

Internal

Internal

Battery Plus

Battery Plus

w/Internal

Battery Plus

Battery Plus

Qty 2

Qty 3

VA

Watt

Battery

EBC 36

EBC 72

EBC 72

EBC 72

30000

27000

11

31

56

89

108

29000

26100

11

33

58

90

109

28000

25200

12

35

60

93

111

27000

24300

12

38

62

95

114

26000

23400

13

40

65

98

118

25000

22500

14

43

68

101

124

24000

21600

14

46

71

103

129

23000

20700

15

48

74

106

134

22000

19800

16

51

76

109

144

21000

18900

17

53

79

111

152

20000

18000

18

56

82

114

160

19000

17100

19

58

85

117

175

18000

16200

20

62

88

120

189

17000

15300

22

66

92

130

204

16000

14400

24

71

96

142

219

15000

13500

26

75

101

154

234

14000

12600

28

79

105

166

249

13000

11700

31

84

110

178

265

12000

10800

35

88

114

201

280

11000

9900

38

94

119

226

319

10000

9000

42

101

134

251

355

7500

6750

58

117

188

347

471

5000

4500

90

188

294

543

610