beautypg.com

Powerware E.T.N 1500 VA - 60kVa User Manual

Page 33

background image

www.powerware.com

1.800.356.5794

SINGLE-PHASE SERIES
Powerware 5125 Rackmount (continued)

POWERWARE POWER DISTRIBUTION UNIT (PDU)

For a list of Powerware PDU models, refer to that section.

POWERWARE ENCLOSURE

See the Powerware Enclosure section for a comprehensive list of IT enclosure offerings.

SOFTWARE AND CONNECTIVITY OPTIONS

Bundled with Software Suite CD and communication cable. See the software and connectivity product section for more detail.

SERVICE PLANS

For service plans, please see the service section beginning on page 88.

POWERWARE RACKMOUNT BATTERY BACK UP TIMES (in minutes)

Standard

Load (VA/Watts)

Internal Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

1000/900

59

169

303

452

612

2000/1800

26

79

138

204

274

2200/1980

21

65

112

164

223

2500/2250

19

61

106

156

210

2700/2430

17

52

89

132

180

3000/2700

15

49

85

125

168

3500/3150

13

43

73

110

142

4500/4050

8

27

52

76

102

5000/4500

7

24

46

67

89

5500/4950

6

22

42

61

81

6000/5400

5

19

36

53

71

Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature etc.