Pvi atmospheric gas water heaters, Typical construction

background image

PV500-2 06/10

1

Section 2

PVI ATMOSPHERIC GAS WATER HEATERS

TYPICAL CONSTRUCTION

MANUFACTURED AFTER JANUARY 1, 1994

Figure 2-1

1. Vent stack *

7. Control switch(es) and fuse(s)

2. Draft diverter (hood)

8. Gas valve

3. Flue damper (on some models)

9. Pilot line

4. Temperature limiting device

10. Drip leg *

(set at 200°F)

11. Gas supply line *

5. Upper operating thermostat

12. Handhole cleanout

(set at 130°F)

6. Operating

thermostat

(set at 120°F)

(* Not furnished by PVI)



CAUTION: TEMPERATURES HIGHER THAN 125°F INCREASE THE RISK OF SCALD INJURY!

IMPORTANT: Clearances to unprotected combustible material must be 8" minimum at top, sides and rear, and 24" in front.
Clearances for servicing and inspection must be 18" minimum at sides and rear and 24" minimum in front.