beautypg.com

Ims-4862 smoke detector sensor, Installation instructions, Introduction – Phonetics IMS-4000 User Manual

Page 143: Cabling, Mounting, Configuration, Introduction cabling mounting configuration

background image

Chapter 7: IMS-4000 Sensors

143

IMS-4862 Smoke Detector Sensor

Installation Instructions

Introduction

The IMS-4862 Smoke Detector Sensor is designed to

connect to the IMS-4000 Host or Node and monitor

for smoke in indoor environments. The electrical

connection between the sensor and IMS-4000 is made

via the attached RJ-45 patch cable. The sensor may be

secured to a wall or ceiling (hardware not included).

Cabling

The Smoke Detector Sensor comes with an attached

7' cable with an RJ-45 plug on the end. If the sensor

is close to the IMS-4000 Host or Node, you can plug the sensor directly to an IMS environmental

input. If the cable is too short you can use the included RJ-45 adaptor and a longer patch cable to

extend the length. For applications where the sensor may be far from the IMS unit, you may utilize

your existing network wiring infrastructure. For example, the sensor may be installed in another

room or another floor. Connect the sensor to your structured wiring network via an RJ-45 jack. At

the other end, connect a patch cable from your structured wiring patch panel directly to the Host or

Node environment input.

!

Caution:

The IMS sensors are not TCP/IP devices and therefore should not be connected

directly to any wiring infrastructure that is connected to network equipment such as a

hub, router, or switch. Sensors use RJ-45 plugs and cables similar to those used with

Ethernet devices.

Mounting

The sensor may be mounted directly against a wall or ceiling (hardware not included).

Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a

new sensor is plugged into the Host or Node, the configuration is set to the factory default via the

Sensor Template.

If you have modified these templates, the configuration will be set to the modi-

fied configuration. When a sensor is removed, or the connection is disrupted, the configuration

data remains intact but the sensor will go into trouble status and generate a trouble alarm. When

the sensor is plugged in again, or the connection is re-established, configuration data remains

unchanged and the sensor returns to normal operating condition.
The smoke alarm is a latching alarm device. To reset the smoke alarm, momentarily disconnect the

cable from the front panel of the IMS Host or Node and then reconnect it.

!

Caution

: Removing a sensor for less than 60 seconds does not produce a trouble alarm.

Removing or unplugging a sensor for more than 60 seconds or plugging in a different

sensor at any time will cause a trouble alarm.