Sidewall direct venting, Vent/air termination – sidewall, Installation & operation manual – Lochinvar KNIGHT 800 User Manual

Page 24: Figure 4-3a clearance to gravity air inlets

background image

Installation & Operation Manual

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

FROM BOILER

VENT PIPE

CONNECTION

TO BOILER

INTAKE AIR

CONNECTION

BIRD SCREEN

Figure 4-1C Alternate Stainless Steel Vent Termination
- Typical Stainless Steel Sidewall Termination of Air and
Vent Models 399 - 600 w/Field Supplied Fittings,
Utilizing FasNSeal’s Hood Intake. Available Through
FasNSeal Only

4

Sidewall direct venting

TO BOILER INTAKE
AIR CONNECTION

FROM BOILER VENT
PIPE CONNECTION

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

Figure 4-2B Alternate Stainless Steel Sidewall
Termination Models 700 - 800 w/Field Supplied Fittings

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

FROM BOILER

VENT PIPE

CONNECTION

TO BOILER

INTAKE AIR

CONNECTION

BIRD SCREEN

BIRD SCREEN

Figure 4-2A Alternate PVC/CPVC Sidewall Termination
Models 399 - 800 w/Field Supplied Fittings

PVC/CPVC or ABS is acceptable air inlet pipe material.

NOTICE

Vent/air termination – sidewall

5.

Maintain clearances as shown in FIG.’s 4-1A thru 4-4B,
pages 23 thru 25. Also maintain the following:
a.

Vent must terminate:

• At least 6 feet (1.8 m) from adjacent walls.
• No closer than 12 inches (305 mm) below roof

overhang.

• At least 7 feet (2.1 m) above any public walkway.
• At least 3 feet (.9 m) above any forced air intake

within 10 feet (3 m).

• No closer than 12 inches (305 mm) below or

horizontally from any door or window or any other
gravity air inlet.

b.

Air inlet must terminate at least 12 inches (305 mm)
above grade or snow line; at least 12 inches (305 mm)
below the vent termination (FIG. 4-1B); and the vent
pipe must not extend more than 24 inches (610 mm)
vertically outside the building.

c.

Do not terminate closer than 4 feet (1.2 m)
horizontally from any electric meter, gas meter,
regulator, relief valve, or other equipment. Never
terminate above or below any of these within 4 feet
(1.2 m) horizontally.

6.

Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.

VENT / AIR

TERMINATION

12"

MIN.

12"

MIN.

12"

MIN.

Figure 4-3A Clearance to Gravity Air Inlets

24

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

12" MIN

15" MAX

12" MIN

Figure 4-1D Alternate PVC/CPVC/SS Vent Termination
- Typical Stainless Steel Sidewall Termination of Air and
Vent Models 399 - 600 w/Field Supplied Fittings,
Utilizing 90° Elbow Intake