Service Manual 45

Troubleshooting Guide

Balance Refrigerant of the 3-way Valve

(Gas leakage)

• Procedure

(1) Confirm that both the 2-way and 3-way

valves are set to the back seat.

(2) Connect the charge set to the 3-way

valve’s port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service

port.

(3) Open the valve (Lo side) on the charge set

and discharge the refrigerant until the
gauge indicates 0 kg/cm

2

G.

– If there is no air in the refrigerant cycle (the

pressure when the air conditioner is not
running is higher than 1 kg/cm

2

G), dis-

charge the refrigerant until the gauge indi-
cates 0.5 to 1 kg/cm

2

G. if this is the case, it

will not be necessary to apply a evacuatin.

– Discharge the refrigerant gradually; if it is

discharged too suddenly, the refrigeration
oil will also be discharged.

Lo

Open

Open

3-Way
valve

3-Way
valve

Gas side

CLOSE

OPEN

Outdoor unit

Liquid side

Indoor unit