Service Manual 33

Operation

Function of Controls

Operation

• DISPLAY

1) C/O Model

Operation Indicator

• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Timer Indicator

• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Comp. Running Incidator

• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compres-

sor off.

2) H/P Model

Operation Indicator

• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)

Timer Indicator

• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.

Defrost Indicator

• OFF except when hot start during heating mode operation or while in defrost control.

Cooling Mode Operation

• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the out-

door fan stop.

• When it reaches 0.5°C above the setting temp, they start to operate again.

Compressor ON Temp

Setting Temp+0.5°C

Compressor OFF Temp

Setting Temp-0.5°C

• While in compressor running, operating with the airflow speed set by the remote control. While in

compressor not running, operating with the low airflow speed regardless of the setting.

Healthy Dehumidification Mode

• When the dehumidification operation input by the remote control is received, the intake air tempera-

ture is detected and the setting temp is automatically set according to the intake air temperature.

26°C

Intake Air Temp

25°C

24°C

Intake Air Temp<26°C

Intake Air Temp-1°C

18°C

Intake Air Temp<24°C

Intake Air Temp-0.5°C

Intake Air Temp<18°C

18°C