beautypg.com

Theory of operation, Engine starting, protection and battery charging, E-2 outback® 185 – Lincoln Electric OUTBACK SVM204-A User Manual

Page 36

background image

THEORY OF OPERATION

E-2

E-2

OUTBACK® 185

ENGINE STARTING, PROTECTION
AND BATTERY CHARGING

ENGINE STARTING
A 12 Volt battery supplies power to the rotary
run/stop/idle switch through a fuse that is located
inside the control box. There is also a lead running
from the fuse to the PC board. This is for battery
charging only.

When the switch is placed in the “Low Idle” or “High
Idle” position, a relay on the PC board is activated.
This relay activates the engine ignition system by
opening a ground lead from the engine magneto.

When the switch is held in the “Start” position, the
starter motor solenoid is activated, cranking the
engine. After the engine starts, the switch is released
and returns to the “high idle” position.

FIGURE E.2 - ENGINE STARTING, PROTECTION AND BATTERY CHARGING

If the battery is too low to properly power the starter
motor, the built-in recoil starter can be used to crank
the engine. (As long as the battery can produce 6 volts
or more, the engine ignition system will remain
enabled.)

NOTE: This machine will only start if there is at least 6
volts available to activate the engine ignition system. If
the battery is removed or completely dead, the engine
will not start.

ENGINE PROTECTION
The Kohler engine has a built-in oil level sensor that is
connected to an oil level module. If the oil level is low,
the ignition magneto is disabled. This will prevent the
engine from starting, or shut it down. Low oil level will
also cause a warning light on the Outback®’s control
panel to flicker for a few seconds when cranking the
engine.

NOTE: Unshaded areas of Block Logic

Diagram are the subject of discussion

+

CB1

CB3

CB2

CB4

__

++

_ +

240 VAC

RECEPTACLE

ENGINE

OIL

LEVEL

MODULE

(KOHLER)

OIL LEVEL

INDICATOR

OIL LEVEL

SWITCH

IGNITION

STATOR

ROTOR

OFF

AUTO

HIGH

START

ALTERNATOR

IDLE

SOLENOID

SLIP

RINGS

AUXIIARY WINDINGS

WELD

WINDINGS

REACTOR

EXCITER

WINDING

CURRENT

SENSOR

120 VAC RECEPTACLES

BOOST

WINDING

OUTPUT

RECTIFIER

(2 PHASE)

CHOKE

OUTPUT

STUDS

BATTERY

ENGINE

SHUTDOWN

RELAY

HOUR

METER

FIELD / CONTROL PC BOARD

AUTOMATIC

IDLER

CIRCUIT

OUTPUT

CONTROL CIRCUIT

OUTPUT

CONTROL

10 AMP

FUSE

STARTER

/

SOLENOID

BRUSHES

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC