CHIMNEY INSTALLATION INSTRUCTIONS

1. Cut and frame the holes in the ceiling,

floor and roof where the chimney will pass

(see Figure 19). Use a plumb-bob to line

up the center of the holes. The hole sizes

are indicated in Table 3 for the floor and

ceiling holes and in Table 4 (Page 17) for

the roof holes.

Figure 19

2. From below, install a firestop in each ceiling/

floor separation through which the chimney

will pass. At the attic level, install an attic

radiation shield from above (see Figures

20A and 20B).

3. For ASHT+ and S-2100+ chimneys, place

the first chimney length on the fireplace. To

lock it into place, turn 1/4 of a turn clock-

wise. With the AC chimney you must use

a starting section before installing the first

chimney length (see Figure 21). Continue

installing chimney lengths making sure to

lock each length in place.

4. Every time the chimney passes through a

roof or a wall, install the appropriate firestop.

When you reach the desired height, install

the roof support (see instructions included

with the support).

5. Then, put the roof flashing in place and seal

the joint between the roof and the flashing

with roofing pitch. For sloping roofs, place

the flashing under the upper shingles and on

top of the lower shingles. Nail the flashing

to the roof, using roofing nails (Figures 22

and 23).

6. Place the storm collar over the flashing and

tighten it with the bolt supplied. Finally, seal

the joint between the storm collar and the

chimney, using silicone caulking.

7. Install the chimney cap. Once the chimney

cap is in place, the roof flashing can be

washed with a solvent or vinegar and then

painted with rust-proof paint.

Figure 20A

Figure 20B

CHIMNEY MODEL

8"

SQUARE HOLE

SIZE OPENING

ASHT+ / HT6103+

14-3/8” (365 mm)

S-2100+ / HT6000+

16” (406 mm)

AC

15" (380 mm)

Note: See Table 4 for Sloped Roof Framing

Table 3 - Flat Roof Framing

Figure 21

Attic Radiant

Firestop

Firestop

ASHT+ and S2100+

AC

Air Cooled Pipe

AC RSA

AC RS

Cooling Air Kit For Air

Cooled Chimney ACZI

(required when

using AC chimney)

AC CHIMNEY INSTALLATION
(AIR COOLED INSULATED GALVALUME CHIMNEY)

Outside Combustion

Air Kit (UZI)

AC Air Cooled

Chimney Starting Piece

Radiation

Shield

Attic Radiation

Shield

Support

Flashing

Rain Cap

Flashing Collar

Note: The outside air kit is mandatory

for both fireplace and chimney