Table 4 battery cabinet specifications, Table 4, Battery cabinet specifications – Liebert PSITM User Manual
Page 31

Specifications
27
Agency
Safety
EN 62040-1-1; TUV/GS listed; CE compliance mark
Surge
EN61000-4-5, Level 3, Criteria B
ESD
EN61000-4-2, Level 3, Criteria B
Susceptibility
EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient
EN61000-4-4, Level 4, Criteria A
Emissions
EN 50091-2, Class B
Conducted Immunity
EN61000-4-6
Harmonics
EN61000-3-2
Flicker
EN61000-3-3
Transportation
ISTA Procedure 1A Certification
Table 4
Battery cabinet specifications
Model Number
PS2-48VBATT
PS2-72VBATT
Used w/UPS Model
PS1000RT2-230
PS1440RT2-230
PS2200RT2-230
PS3000RT2-230
Dimensions, W x D x H, mm (in)
Unit
87 x 557 x 430 (3.43 x 22 x 17)
87 x 612 x 430 (3.43 x 24.1 x 17)
Shipping
300 x 706 x 598
(11.8 x 27.8 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
Weight, kg (lbs)
Unit
30 (66.1)
46 (101.4)
Shipping
38.6 (85.1)
53.6 (118.1)
Battery Parameter
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating
2 strings of 4 x 12V x 7Ah
2 strings of 6 x 12V x 9Ah
Battery Manufacturers
CSB, B&B Battery and EnerSys
Backup Time
See Table 5 - Battery run times
Environmental
Operating Temperature
0°C to + 40°C (+32°F to + 104°F)
Storage Temperature
-15°C to + 40°C (+5°F to + 104°F)
Relative Humidity
0% to 95%, non-condensing
Operating Altitude
Up to 3,000m (10,000 ft) at 35°C (95°F) without derating
Agency
Safety
EN 62040-1-1; TUV/GS listed; CE compliance mark
Emissions
EN 50091-2, Class B
Transportation
ISTA Procedure 1A Certification
Table 3
UPS specifications (continued)
Model Number
PS1000RT2-230
PS1440RT2-230
PS2200RT2-230
PS2200RT2-230E
PS3000RT2-230
PS3000RT2-230E