beautypg.com

0 voltage programming procedure, Figure 17 load level indicators, Oltage – Liebert PSITM User Manual

Page 25: Rogramming, Rocedure

background image

Voltage Programming Procedure

21

9.0

V

OLTAGE

P

ROGRAMMING

P

ROCEDURE

Figure 17 Load Level Indicators

1. Remove the front bezel from the UPS.
2. UPS must be operating in Normal (AC) mode.

3. The AC Input, Load, and Battery Level Indicators should be lit.
4. Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode.

The UPS will beep and all of the indicators on the front panel display will flash on and off for

approximately 5 seconds. The next cycle will display the current configuration, either 220, 230 or

240 VAC. One of the Load Level Indicators will be flashing. Initially, the 0%-25% Load Level

Indicator will be flashing, indicating the default setting of 230V as shown in Figure 17.

5. Press the ON button to step through the voltage settings until the appropriate Load Level

Indicator is flashing.

6. Press the Voltage Programming button. The UPS will return to Normal mode operation.
The Voltage Programming button allows the operator to select the mains transfer voltage at which

the UPS will switch to battery power. This also changes the inverter voltages. The voltage settings

are as follows:

NOTE
Mains power will be applied to the connected load.

Setting

Input Voltage

Range

Output Voltage

(Battery Mode)

120V (230V)

166 - 272VAC

(default)

230VAC

110V (220V)

158 - 260VAC

220VAC

127V (240V)

172 - 283VAC

240VAC

Load Level

Indicators

Voltage

Programming

Button