Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Rem Ctrl Flt

External control is cycling too often.

• Check set point of the external control.

• Check the wiring between the external control and the
unit.

• Replace the control.

Parameters

Progr

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM

display

to reset.)

After downloading parameters from a laptop,
the main control board must be reset.

• Press the ENTER/RESET button on the SMART
SYSTEM display panel.

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.

• Establish a heating load to remove the heat from the
boiler

loop.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the

Knight XL Installation and Operation

Manual for the proper piping methods for the Knight
XL

boiler.

• Check 120 vac to the boiler pump motor on a call for
heat. If voltage is not present, check the wiring back
to the main control board. Replace the main control
board if necessary.

• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.

• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight
XL Installation and Operation Manual for boiler
pump

specifications.

Low 24 vac

120 vac input to the main control board has
dropped below 80 vac.

• Check 120 vac supply to the transformer.

Check wiring connections at the low voltage

terminal

strip.

• Check the wire size/length to remote devices.

• Replace the transformer.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Replace the main control board.

Service Manual