beautypg.com

3 rj-45 data line protection connectors, 4 ups communications, 5 ups inverter/transfer voltage configurations – Liebert UPS Systems PSI XR User Manual

Page 23: Figure 17 dip switch settings for 120v system, Table 5 voltage configurations, Rj-45 data line protection connectors, Ups communications, Ups inverter/transfer voltage configurations, Table 5, Voltage configurations

background image

Communication

19

6.3

RJ-45 Data Line Protection Connectors

Data line (in and out) connectors on the rear of the UPS provide transient voltage surge suppression

(TVSS) for network devices.

6.4

UPS Communications

The Liebert PSI XR is equipped with a Liebert IntelliSlot

®

port to provide advanced communication

and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server

via USB and RS-232 in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across

the network.

6.5

UPS Inverter/Transfer Voltage Configurations

A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt-

ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS

switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat-

tery mode. The factory default setting is 120 VAC.

Figure 17 DIP switch settings for 120V system

NOTE
The USB, SNMP and contact closure communications operate in parallel. Using the Liebert

IS-WEBRT3 disables the serial communications of the DB-9.

Table 5

Voltage configurations

Setting

Input Voltage Range

Output Voltage (Battery Mode)

110

83~138

110VAC

120

90~150

120VAC

127

96~159

127VAC

1

2

DIP ON

FUNCTION

Voltage = 110V

Voltage = 120V

Voltage = 120V

Voltage = 127V

1

2