Communication
19
6.3
RJ-45 Data Line Protection Connectors
Data line (in and out) connectors on the rear of the UPS provide transient voltage surge suppression
(TVSS) for network devices.
6.4
UPS Communications
The Liebert PSI XR is equipped with a Liebert IntelliSlot
®
port to provide advanced communication
and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server
via USB and RS-232 in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across
the network.
6.5
UPS Inverter/Transfer Voltage Configurations
A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt-
ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS
switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat-
tery mode. The factory default setting is 120 VAC.
Figure 17 DIP switch settings for 120V system
NOTE
The USB, SNMP and contact closure communications operate in parallel. Using the Liebert
IS-WEBRT3 disables the serial communications of the DB-9.
Table 5
Voltage configurations
Setting
Input Voltage Range
Output Voltage (Battery Mode)
110
83~138
110VAC
120
90~150
120VAC
127
96~159
127VAC
1
2
DIP ON
FUNCTION
Voltage = 110V
Voltage = 120V
Voltage = 120V
Voltage = 127V
1
2