Table 8 power distribution specifications, Table 9 external battery cabinet specifications, Table 8 – Liebert GXT2-6000RT230 User Manual
Page 37: Power distribution specifications, Table 9, External battery cabinet specifications

Specifications
33
Table 8
Power distribution specifications
Model Number
PD-CEHDWR
PD-CEHDWRBYP
Amps Rating
32 Amps
Input Power Connection
3-Wire Hardwired, 6-10mm
2
(8-10AWG)
Output Power Connection
3-Wire Hardwired, 6-10mm
2
(8-10AWG)
Includes: Two IEC320 C19 16A/250V sockets
Two IEC320 C19 16A/250V sockets
Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker
32A, Supplied by User
Table 9
External battery cabinet specifications
Model Number
GXT2-240VBATT
Used w/ UPS model
GXT2-6000RT230, GXT2-4500RT230
Dimensions, W x D x H, mm (in.)
Unit (with bezel)
176 x 522 x 430 (6.9 x 20.55 x 16.9)
Shipping
560 x 690 x 455 (22 x 27.2 x 17.9)
Weight, kg (lbs)
Unit
65 (145)
Shipping
78.5 (173.1)
Battery Parameters
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V
20 x 12V
Battery Manufacturer, Part #
Yuasa / REW 45-12
Backup Time
See Battery Run Times charts
Environmental
Operating Temp
0
°C to +40°C (+32°F to +104° F)
Storage Temp
-15
°C to +50°C (+5°F to +122° F)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 2000m (6600 ft.) at 40
°C (104° F) without derating
Storage Elevation
15,000m (50,000 ft.) maximum
Agency
Safety
EN62040-1-1; TUV/GS
Transportation
ISTA Procedure 1B