beautypg.com

Table 5 alarm conditions, Table 5, Alarm conditions – Liebert GXT2-6000RT230 User Manual

Page 33

background image

Troubleshooting

29

Fault and LEDs D&E are

Illuminated

Charger malfunction

If the charger is overvoltage, the UPS will shutdown. If the

charger is undervoltage and the batteries are nearly depleted,

this alarm will give a temporary warning before the UPS shuts

down. UPS requires service. Contact your local dealer, Liebert

representative or Liebert Worldwide Support Group.

Battery LED is flashing.

Battery source is not

available; continuous horn.

Check battery connections, completely power down and restart

UPS.

NOTE: If the battery circuit

opens while the UPS is running,

it will be detected when the next

battery test is performed.

Table 5

Alarm conditions

Condition

Alarm

Battery Mode (mains failure)

One short beep every 10 seconds: more than 2 minutes of run time remaining

Low Battery

Two short beeps every 5 seconds: less than 2 minutes of run time remaining

Output Overload (Bypass)

One short beep every half second

Overtemperature (Bypass)

A one-second beep every 4 seconds

DC Bus Overvoltage (Bypass)

A one-second beep every 4 seconds

DC-DC failure during battery

mode

A one-second beep every 4 seconds

PFC Failure (Bypass)

A one-second beep every 4 seconds

Inverter Failure

A one-second beep every 4 seconds

Battery Test Failure

A two-second beep every 1 minute

Fan Locked

A one-second beep every 4 seconds

REPO Active

A 0.25-second beep every 0.25 seconds

UPS OFF; Autorestart disabled

from previous REPO shutdown

A one-second beep every 4 seconds

Charger Malfunction

A one-second beep every 4 seconds

Table 4

Troubleshooting guide (cont’d)

Problem

Cause

Solution

This manual is related to the following products: