beautypg.com

Hydronic piping, Flow rate (gpm), Temperature rise applications – Lochinvar KNIGHT 399 - 800 User Manual

Page 37

background image

Installation & Operation Manual

37

6

Hydronic piping

(continued)

Figure 6-5 Pressure Drop vs. Flow - Models 399 and 500

Table 6B Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F

Figure 6-6 Pressure Drop vs. Flow - Models 600 thru 800

0

2

4

6

8

10

12

14

16

18

20

0

5

10

15

20

25

30

35

40

45

KBN500

KBN399

Pressure Drop vs Flow

(Includes Boiler Secondary Piping)

Flow Rate (GPM)

Pressure Drop (Feet of Head)

0

10

20

30

40

50

60

0

10

20

30

40

50

60

70

80

90

KBN800

KBN700

KBN600

Pressure Drop vs Flow

(Includes Boiler Secondary Piping)

Flow Rate (GPM)

P

ressur

e Dr

op (F

eet of Head)

TEMPERATURE RISE APPLICATIONS

Model

MINIMUM

PIPE

SIZE

20°F

25°F

30°F

35°F

GPM

FT/HD

GPM

FT/HD

GPM

FT/HD

GPM

FT/HD

399

1 1/2"

37

21

30

14

26

11

21

8

500

1 1/2"

46

23

37

16

32

13

26

10

600

2"

55

31

44

22

38

18

32

13

700

2"

65

30

52

20

45

16

37

11

800

2"

74

33

60

23

51

18

42

12