Ic series, Lens, 2s va 6u – Lightolier IC Series User Manual
Page 2: Options/accessories, Specifications, Specifications (continued), Ordering information, Page 2 of 2, Job information type

Lens
IC Series
Page 2 of 2
2' x 2' Recessed Fluorescent, IC Lens Frame Troffer
Static, 2-6" U Lamp T8
IC
Standard IC Lens
IY
For NYC Code – I.B.E.W. Manufactured
0.0
45.0
90.0
FLUX
0
1708
1708
1708
5
1700
1698
1702
162
15
1620
1635
1655
462
25
1467
1501
1531
691
35
1231
1274
1328
798
45
904
959
1069
748
55
553
592
651
531
65
313
269
331
302
75
173
141
207
180
85
59
54
68
63
90
0
0
0
Model No. ICS2GFSVA26U120SO
LER = FP - 58.4
IW - 56.5
BF - 0.87
Comparative yearly lighting energy cost per
1000 lumens = $3.86
Report Number: G00036
Catalog Number: ICS2GFSVA26U120SO
Lamp: (2) T8 U6
Luminaire: IC 2' X 2' with VA lens
Ballast: M2-RN-T81LL-D-120
Report is based on 2750 Lumens per lamp.
Efficiency: 71.6%
CIE Type-Direct-Indirect
Plane:
0-Deg
90-Deg
Spacing Criteria:
1.2
1.2
Shielding Angles:
90
90
Plane:
0-Deg
90-Deg
Luminous Length:
21.720
21.720
CANDELA DISTRIBUTION
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG.
0-DEG.
45-DEG.
90-DEG.
45
4199.
4454.
4565.
55
3167.
3390.
3728.
65
2432.
2091.
2572.
75
2195.
1789.
2627.
85
2223.
2035.
2563.
LUMINANCE DATA IN CANDELA/SQ. METER
ZONE
LUMENS % LAMP
% FIXT
0
0-
0
30
1315
23.9
33.4
0
0-
0
40
2113
38.4
53.7
0
0-
0
60
3392
61.7
86.1
0
0-
0
90
3938
71.6
100.0
90-180
000
0
0.0
00
0.0
0
0-180
3938
71.6
100.0
ZONAL LUMEN SUMMARY
Mounting Height
Lengthwise
Crosswise
Room
Luminaires
Luminaires
Size
0 Deg Plane
90 Deg Plane
8.5 10 13 16
8.5 10 13 16
30x30
50 54 58 63
47 51 55 60
40x40
47 50 53 56
44 47 50 53
60x30
52 56 60 64
51 55 58 62
60x60
44 46 47 50
41 43 44 48
100x100
44 44 43 45
42 41 40 41
TYPICAL V.C.P.'s
Options/Accessories
Special Lenses: Substitute VY for VA (standard) = .125" nominal pattern 12 with 7.8 oz. average weight per
square foot. Substitute VI for VA (standard) = .125" nominal pattern 12 with 6.8 oz. average weight per
square foot.
Radio Interference Filter: To order one RIF per fixture; SUFFIX: R.
To order one RIF per ballast; SUFFIX: B.
Electrical Wiring Options: Consult factory.
Drywall Kit: Order Catalog Number: FK92X2. (Request Folio OA30-10 Rev. A).
Chicago Plenum: SUFFIX: C.
Specifications
Performance: In an installation of 2 lamp 31W luminaires in a room cavity ratio of 1, reflectance
80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .76. To prevent glare the VCP shall
be not less than 41 either lengthwise or crosswise (at 100fc level) and the average brightness at 65°
shall not exceed 2572 candelas per square meter. To control veiling reflections, luminaire output in
the 30°-90° zone shall not be less than 66.9%.
Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing with side rails hemmed
over and housing ends turned-in for safe handling.
Specifications (continued)
Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel
minimum 86% reflectance. Rust preventative undercoating.
Lenses: VA (standard) extruded virgin acrylic, 3/16" square based female cones, running 45° to the
panel edge, .095" nominal thickness (similar to pattern 12). VY (optional) .125" nominal pattern 12
with 7.8 oz. average weight per square foot. VI (optional) .125" nominal pattern 12 with 6.8 oz. aver-
age weight per square foot.
Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of
ballast, use wire suitable for at least 90°.
Labels: I.B.E.W. UL and ULc Listed.
This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See:
www.lamprecycle.org
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
0
RC
80
50
30
RW 70 50 30 50 30 10 50 30 10
1
79 76 73 71 69 67 68 66 65
2
72 67 62 63 60 57 61 58 55
3
66 60 54 56 52 49 54 51 48
4
61 53 48 51 46 42 49 45 42
5
57 48 42 46 41 37 44 40 37
6
53 44 38 42 37 33 41 36 33
7
49 40 34 38 33 29 37 33 29
8
46 36 31 35 30 26 34 30 26
9
43 34 28 32 27 24 32 27 24
10 40 31 26 30 25 22 29 25 22
IC Series:
Recessed Lens
suitable for
Direct Thermal
Insulation
Contact
Body Style:
S=Static
Fixture
Width
Lens Shielding
Type:
VA=Virgin acrylic (standard),
see options and
consult factory
Voltage:
120, 277 or
UNV=120-277
Ceiling Type:
G= Grid
(lay-in T bar)
T= Slot grid
Lens Frame:
FS= Flat steel frame.
RA=Regressed
aluminum
frame.
FA= Flat aluminum
frame.
Lamp Type/
Fixture Length:
(By Others)
6U=6"U Lamp T8
(Nominal 24")
Lamp
Quantity
2=2 lamps
Ballast Type:
<20THD <10THD
1-2 Lamp Elec. T8
SO *
H
I *
†
*Instant Start Standard
NOTE:
For T8 UNV, you must use H
I Ballast Code.
2
S
VA
6U
Options:
Lamps
Flex
EM Pack
Fuse
(Consult your
representative)
Ordering Information
Explanation of Catalog Number. Example: ICS2GFSVA26UUNVHI
-
Job Information
Type:
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595
08/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.