Chapter 9. Basic functions
CHAPTER 9 -
Basic Functions
9.1
Frequency mode
z Digital Frequency setting via Keypad 1
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
Command] - 0/400
0.0 Hz
Drive
group
Frq
[Frequency mode]
0
0/8 0
Run frequency is settable in 0.0 - [Frequency Command].
Set
Frq – [Frequency mode] to 0 {Frequency setting via Keypad 1}.
Set the desired frequency in 0.0 and press the Prog/Ent (z) key to enter the value into memory.
The value is settable not greater than F21 – [Max frequency].
z Digital Frequency setting via Keypad 2
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
Command] - 0/400
0.0 Hz
Drive
group
Frq
[Frequency mode]
1
0/8 0
Run frequency is settable in 0.0 - [Frequency Command].
Set
Frq – [Frequency mode] to 1{Frequency setting via Keypad 2}.
In
0.0, frequency is changed upon pressing the Up (
S)/Down (T) key. It is selected to use the
Up/Down key as potentiometer on keypad.
The value is settable not greater than F21 – [Max frequency].
60