Chapter 6. Basic operation
Frequency setting via potentiometer & operating via the Run key
1
-. Apply AC input power to the inverter.
2
-. When 0.0 is displayed, press the Up (
S) key three times.
3
-. drv is displayed. Operating method is selectable. 
-. Press the Prog/Ent (
z) key.
4
-. Check the present operating method (“1” is run via control terminal) 
-. Press the Prog/Ent (
z) key and then Down (T) key once.
5
-. After setting “0”, press the Prog/Ent (
z) key.
6
-. “drv” is displayed after “0” is blinking. Operation method is set via the Run key on the 
keypad. 
-. Press the Up (
S) key once.
7
-. Different frequency setting method is selectable in this code. 
-. Press the Prog/Ent (
z) key.
8
-. Check the present frequency setting method (“0” is run via keypad). 
-. Press the Up (
S) key twice.
9
-. After checking “2” (frequency setting via potentiometer), press the Prog/Ent (
z) key.
10
-. “Frq” is displayed after “2” is blinking. Frequency setting is set via the potentiometer on 
the keypad. 
-. Turn the potentiometer to set to 10.0 Hz in either Max or Min direction. 
11
-. Press the Run key on the keypad. 
-. FWD lamp begins to blink and accelerating frequency is displayed on the LED. 
-. When run frequency 10Hz is reached, 10.0 is displayed as shown left. 
-. Press the STOP/RST key. 
12
-. FWD lamp begins to blink and decelerating frequency is displayed on the LED. 
-. When run frequency is reached to 0Hz, FWD lamp is turned off and 10.0 is displayed as 
shown left. 
220VAC
L1(R)
L2(S)
P
P1
N
G
U
V
W
Motor
MIN
MAX
RUN
STOP/RST
Freq.
Run key
10 Hz
STOP/RST key
Wiring Operating
pattern
41