beautypg.com

Operating information, General – Lochinvar 400 User Manual

Page 61

background image

Installation & Operation Manual

General

How the boiler operates

The Knight XL uses an advanced stainless steel heat exchanger
and electronic control module that allows fully condensing
operation. The blower pulls in air and pushes flue products
out of the boiler through the heat exchanger and flue piping.
The control module regulates blower speed to control the
boiler firing rate. The gas valve senses the amount of air
flowing into the boiler and allows only the right amount of
gas to flow.

How the control module operates

The SMART SYSTEM control module receives inputs from
boiler sensors and external devices. The control module
activates and controls the blower and gas valve to regulate
heat input and switches the boiler, Domestic Hot Water
(DHW), and system pumps on and off as needed. The user
programs the module to meet system needs by adjusting
control parameters. These parameters set operating
temperatures and boiler operating modes. Boiler operation
can be based on boiler outlet water temperature, boiler inlet
water temperature, system temperature, a 0 - 10V signal, or
Modbus, depending on the parameter settings.

Control inputs and outputs

Room thermostat

There are three (3) thermostat connections available on this
control. These inputs tell the boiler to provide water for space
heating. Each thermostat connection has its own set point
and outdoor air reset curve. When multiple thermostats have
a call for heat the control will give priority to the demand with
the highest set point.

Example: Assume that both Room Thermostat 1 and Room
Thermostat 2 have a call for heat. RoomThermostat 1 has a
set point of 110°F. Room Thermostat 2 has a set point of
140°F. The boiler will regulate the system temperature to
140°F until Room Thermostat 2 has been satisfied. Once
Room Thermostat 2 has been satisified the boiler will provide
110°F water to the system.

0 - 10V input (set point or power)

The Knight XL can be controlled by a Building Management
System (BMS) using a 0 - 10 VDC signal. The control can be
configured by the installer to use this signal to either control
set point or firing rate.

The Knight XL can also be programmed to accept a call for
heat from a 0 - 10V signal, reference the Knight XL Service
Manual for a detailed explanation of this procedure.

DHW priority

The SMART SYSTEM control allows the connection of a DHW
thermostat or tank sensor to the low voltage connection board.
When a tank sensor is connected, the DHW thermostat input is
ignored.

DHW / space heating (SH) cycling

If a DHW call for heat is received while a space heating call is in
progress and the DHW is in Normal Mode, the control will start
the DHW pump and shut the boiler pump off. The system
pump will remain on. If the space heating call is still active while
the DHW call is in operation, the control will wait for 30
minutes (time adjustable by installer) then it will switch back to
the space heating demand. There is a timer to switch from space
heating to DHW and a timer to switch from DHW to space
heating. The control will switch back and forth until one of the
heat demands end. This function does not apply to cascade
systems.

Programmable controlling sensor

The control module is programmed to use the outlet sensor as
the control sensor by default. If a system supply sensor is
connected, the control automatically uses it as the control
sensor. The control sensor can be changed by the installer to the
inlet sensor. If the inlet sensor is chosen as the controlling
sensor, it is recommended that the system supply sensor be
installed in the system supply in order to provide the best
control of the inlet temperature.

Anti-cycling

After the burner turns off, the control will delay the next burner
cycle for a set time period (time is adjustable by the installer).
The time delay will be bypassed if the inlet water temperature
drops too far during the delay.

Boiler and system pump control

The boiler pump will run whenever the burner is firing, unless
the DHW is programmed for Normal Mode and the boiler is
heating the DHW tank. The boiler pump will run during Freeze
Protection Mode as well. It will continue to run for a short time
after the burner turns off or the Freeze Protection Mode ends.

The system pump will run whenever there is a space heating call
for heat, or the boiler goes into Freeze Protection Mode. It will
continue to run for a short time after the end of the heat
demand or the Freeze Protection Mode. The system pump can
be programmed to run continuously if desired. In either case, it
will not run during outdoor shutdown.

Temperature control

Modulation

The Knight XL is capable of modulating its firing rate from a
minimum of 20% to a maximum of 100%. The firing rate is
dictated by the call for heat (i.e., space heating or domestic hot
water), the heating load, ramp delay (if enabled), and various
other temperature limitations.

11

Operating information

61

ƽ CAUTION

When multiple temperature loops are
used, thermostatic mixing valves are
required for the protection of any low
temperature loops.

This manual is related to the following products: