Hydronic piping, Installation & operation manual – Lochinvar 400 User Manual
Page 44
Installation & Operation Manual
44
6
Hydronic piping
EXPANSION
TANK
AIR SEPARATOR
PRESSURE REDUCING
VALVE
BACK FLOW
PREVENTER
BALL VALVE
(TYPICAL)
UNION (TYPICAL)
PRESSURE RELIEF
VALVE
FLOW CHECK
VALVE (TYPICAL)
INDIRECT DHW
TANK
BOILER 1
(LEADER)
TEMPERATURE /
PRESSURE GAUGE
PRESSURE GAUGE
DRAIN
DRAIN POINT
(TYPICAL)
BOILER CIRCULATOR
(TYPICAL)
ANTI-SCALD
MIXING VALVE
SYSTEM SUPPLY SENSOR
(WHEN USED)
SYSTEM CIRCULATOR
NO
T T
O
EX
CE
ED
4
PI
PE
DI
A.
OR
M
AX
. O
F 1
2"
AP
AR
T
BOILER 2
(MEMBER 1)
BOILER 3
(MEMBER 2)
BOILER 4
(MEMBER 3)
DOMESTIC
HOT WATER
CIRCULATOR
COLD WATER IN
HOT WATER OUT
MAKE UP WATER
Y-STRAINER
(TYPICAL)
(RECOMMENDED)
MAY SUBSTITUTE
LOW LOSS HEADER
FR
OM
SY
ST
EM
TO
SY
ST
EM
Figure 6-10 Multiple Boilers - Primary/Secondary Piping
Model
Number of Units
2
3
4
5
6
7
8
Manifold Pipe Sizes in Inches (mm)
400
2 1/2 (64)
3 (76)
3 1/2 (89) 4 (102) 4 (102) 5 (127) 6 (152)
501
3 (76)
3 1/2 (89) 4 (102)
5 (127) 5 (127) 6 (152) 6 (152)
601
3 1/2 (89) 4 (102)
5 (127)
5 (127) 6 (152) 6 (152) 8 (203)
701
3 1/2 (89) 5 (127)
5 (127)
6 (152) 6 (152) 8 (203) 8 (203)
801
4 (102)
5 (127)
5 (127)
6 (152) 8 (203) 8 (203) 8 (203)
NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.
NOTICE
CAUTION
Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler
output does not not exceed indirect water heater transfer capabilities.