Hydronic piping

EXPANSION
TANK

AIR SEPARATOR

PRESSURE REDUCING

VALVE

BACK FLOW

PREVENTER

BALL VALVE
(TYPICAL)

UNION (TYPICAL)

PRESSURE RELIEF
VALVE

FLOW CHECK

VALVE (TYPICAL)

INDIRECT DHW

TANK

BOILER 1
(LEADER)

TEMPERATURE /
PRESSURE GAUGE

PRESSURE GAUGE

DRAIN

DRAIN POINT

(TYPICAL)

BOILER CIRCULATOR

(TYPICAL)

ANTI-SCALD

MIXING VALVE

SYSTEM SUPPLY SENSOR

(WHEN USED)

SYSTEM CIRCULATOR

NO

T T

O

EX

CE

ED

4

PI

PE

DI

A.

OR

M

AX

. O

F 1

2"

AP

AR

T

BOILER 2
(MEMBER 1)

BOILER 3
(MEMBER 2)

BOILER 4
(MEMBER 3)

DOMESTIC

HOT WATER

CIRCULATOR

COLD WATER IN

HOT WATER OUT

MAKE UP WATER

Y-STRAINER
(TYPICAL)
(RECOMMENDED)

MAY SUBSTITUTE

LOW LOSS HEADER

FR

OM

SY

ST

EM

TO

SY

ST

EM

Figure 6-10 Multiple Boilers - Primary/Secondary Piping

Model

Number of Units

2

3

4

5

6

7

8

Manifold Pipe Sizes in Inches (mm)

400

2 1/2 (64)

3 (76)

3 1/2 (89) 4 (102) 4 (102) 5 (127) 6 (152)

501

3 (76)

3 1/2 (89) 4 (102)

5 (127) 5 (127) 6 (152) 6 (152)

601

3 1/2 (89) 4 (102)

5 (127)

5 (127) 6 (152) 6 (152) 8 (203)

701

3 1/2 (89) 5 (127)

5 (127)

6 (152) 6 (152) 8 (203) 8 (203)

801

4 (102)

5 (127)

5 (127)

6 (152) 8 (203) 8 (203) 8 (203)

NOTICE

System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in
operation to prevent short cycling and high limit issues.

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

CAUTION

Indirect water heaters are capable of transferring a limited number of Btu’s into the water. Ensure boiler
output does not not exceed indirect water heater transfer capabilities.