Installation Drawings

37

Figure 25 Control wiring for the input contact isolator board option

PS213002 Rev. 2

INPUT CONTACT ISOLATOR BOARD

8. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL

DIAGRAM FOR LOCATION OF INPUT CONTACT ISOLATOR BD. OPT.

5. REFER TO STATIC TRANSFER SWITCH CONTROL CONNECTION

SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS

4. ALL CONTROL WIRING (BY OTHERS) MUST BE RUN

SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

MANUAL FOR CONFIGURING THE INPUT CONTACT ISOLATOR

3. REFER TO INSTALLATION,

OPERATION & MAINTENANCE

2. CUSTOMER PROVIDED NORMALLY OPEN DRY CONTACTS

1. CUSTOMER CONTROL WIRING CONNECTION POINTS ARE

7. MAXIMUM CABLE LENGTH 500 FT. (152 METERS) WITH

6. SIGNAL VOLTAGE: 100mAMP @ 12VDC.

FOR USER ALARM MESSAGES.

AND LOCAL ELECTRICAL CODES.

#16AWG FLEXIBLE STRANDED CABLE.

TERMINALS 1 THROUGH 16 (SEE TABLE J51).

NOTES:

02-810012-XX

BOARD OPTION.

2

3

1

PIN NO.

TABLE (J51)

INPUT

2

1

5

3

4

6

7

J51

14

11

9

8

10

12

13

15

16

"NO CUSTOMER CONNECTION"

CONTACT

1 2 3 4

6

5

4

9 10

7 8

5 6

11 12

7

8

15 16

14

13