SENTRIC KL Switch Disconnectors with Fuses

General data

7

Area of application

SENTRIC KL switch disconnectors with fuses protect against
overload and short-circuits as main control and EMERGENCY-
STOP switches of switchpanels, distribution boards, power sup-
ply and motor feeders. In conjunction with SITOR semiconductor
protection fuses, they are also used in UPS systems, frequency
converters and capacitor control systems.

For use in the paper and pulp processing industry, a special
variant that is resistant to strongly sulphurous atmospheres can
be supplied.

All SENTRIC KL switch disconnectors are climate-proof and
meet the requirements of IEC 60947-1, IEC 60947-3 and
VDE 0660 Part 107.

Technical specifications

1) Technical specifications for CSA approval on request.

2) With 3KL61 for operation –25 °C ... +35 °C, at +55 °C: I

th

= 570 A.

3) Configuring note: max. permissible operating temperature for fuse blades

135°C, for connections 100 °C.

4) 3ND1 switchgear protection fuses.

5) AC-23B.

6) At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.

7) L/R = 2.5 ms.

8) At 440 V DC-22A, at 220 V DC-23A.

Standards

IEC 60 947-1, IEC 60 947-3, VDE 0660 Part 107

Type

3KL50

3KL52

3KL53

3KL55

1)

3KL57

1)

3KL61

1)

3KL62

1)

Rated uninterrupted current I

u

A

63

125

160

250

400

630

800

For fuse links to DIN 43620
(when semiconductor fuse links are used, derating is nec-
essary, see Catalog SITOR Configuration SENTRIC KL
Switch Disconnectors with Fuses
Order No. E20001–A700–P302-X-7600)

Size

00 and
000

00 and
000

00 and
000

1 and 2

1 and 2

3 and 2

3 and 2

Continuous thermal current I

th

3)

A

63

125

160

250

400

630

800

Rated insulation voltage

U

i

V

690

1000

1000

1000

1000

1000

1000

Rated impulse withstand voltage

U

imp

kV

6

8

8

8

8

8

8

Rated operating voltage

U

e

AC 50 Hz/60 Hz

V

690

DC

V

440 (3 conducting paths series-connected),
220 (2 conducting paths series-connected)

Rated short-circuit making capacity with fuses

2)

at AC 50 Hz/60 Hz 690 V

kA (peak value)

220

220

220

176

176

105

105

Rated conditional short-circuit current with fuses

2)

at AC 50 Hz/60 Hz 690 V

kA (rms value)

100

100

100

80

80

50

50

Max. rated current I

n

of the fuses

A

80

160

160

400

400

630

800

Max. permissible power loss of the installed fuse
NH

W

6

9

11.5

32

45

48

62

BS

W

8 (A2/A3)

11.5 (A4)

11.5

32

45

48

60.5

Permissible let-through current of the fuses

kA

8

17

17

30

4)

30

4)

50

50

Maximum permissible cut-off I

2

t value

kA

2

s

55

223

223

1000

1000

5400

10500

Switching capacity (infeed top or bottom)

at AC 400 V
Breaking current I

c

(p.f.

= 0.35)

A (rms value)

500

1000

1280

2000

3200

5100

6400

Rated operating current I

e

at AC-21A, AC-22A, AC-23A

A

63

125

160

250

400

630

5)

800

5)

Motor switching capacity at AC-23A

kW

30

65

80

132

200

335

400

at AC 500 V
Breaking current I

c

(p.f.

= 0.35)

A (rms value)

500

1000

1280

2000

3200

5100

6400

Rated operating current I

e

at AC-21A, AC-22A, AC-23A

A

63

125

160

250

400

630

5)

630

5)

Motor switching capacity at AC-23A

kW

40

90

110

185

280

425

500

at AC 690 V
Breaking current I

c

(p.f.

= 0.35)

A (rms value)

500

1000

1280

2000

3200

5100

6400

Rated operating current I

e

at AC-21A, AC-22A, AC-23A

A

63

125

160

250

400

630

5)

800

5)

Motor switching capacity at AC-23A

kW

50

110

150

220

375

560

700

at DC 440 V (3 series-connected current path)
Breaking current I

c

(L/R = 15 ms)

A

250

500

640

100

6)

1600

2520

7)

2520

7)

Rated operating current I

e

at DC-23A

A

63

125

160

250

8)

400

630

8)

630

8)

Rated short-time current (1 s current)

kA (rms value)

2.5

3.2

3.2

8

11

32

32

Permissible load
depending on the ambient temperature for open-type instal-
lation in switchboards (e.g. 8NA1) in switchgear cubicles or
switchgear racks at
35 °C

A

63

125

160

250

400

630

800

40 °C

A

63

125

155

250

390

630

780

45 °C

A

63

125

150

250

380

610

760

50 °C

A

63

125

145

250

370

590

740

55 °C

A

63

125

140

240

360

570

720

Permissible ambient temperature

°C

–25 ... +55 for operation

4)

, –50 ... +80 for storage

Mechanical endurance

Operations

15000

15000

15000

12000

12000

3000

3000

Required operating torque

Nm

3

7.5

7.5

16

16

30

30

Degree of protection

IP00/IP20 (from operator side, with fuse and terminal covers)

Power loss of the disconnector at I

th

(plus power loss of the fuses)

W

8.5

22

36

33

86

140

225