Sentric kl switch disconnectors with fuses, General data – Siemens AC-21A User Manual
Page 22
Siemens LV 10 · 2004
7/22
SENTRIC KL Switch Disconnectors with Fuses
General data
7
■
Area of application
SENTRIC KL switch disconnectors with fuses protect against
overload and short-circuits as main control and EMERGENCY-
STOP switches of switchpanels, distribution boards, power sup-
ply and motor feeders. In conjunction with SITOR semiconductor
protection fuses, they are also used in UPS systems, frequency
converters and capacitor control systems.
For use in the paper and pulp processing industry, a special
variant that is resistant to strongly sulphurous atmospheres can
be supplied.
All SENTRIC KL switch disconnectors are climate-proof and
meet the requirements of IEC 60947-1, IEC 60947-3 and
VDE 0660 Part 107.
■
Technical specifications
1) Technical specifications for CSA approval on request.
2) With 3KL61 for operation –25 °C ... +35 °C, at +55 °C: I
th
= 570 A.
3) Configuring note: max. permissible operating temperature for fuse blades
135°C, for connections 100 °C.
4) 3ND1 switchgear protection fuses.
5) AC-23B.
6) At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.
7) L/R = 2.5 ms.
8) At 440 V DC-22A, at 220 V DC-23A.
Standards
IEC 60 947-1, IEC 60 947-3, VDE 0660 Part 107
Type
3KL50
3KL52
3KL53
3KL55
1)
3KL57
1)
3KL61
1)
3KL62
1)
Rated uninterrupted current I
u
A
63
125
160
250
400
630
800
For fuse links to DIN 43620
(when semiconductor fuse links are used, derating is nec-
essary, see Catalog SITOR Configuration SENTRIC KL
Switch Disconnectors with Fuses
Order No. E20001–A700–P302-X-7600)
Size
00 and
000
00 and
000
00 and
000
1 and 2
1 and 2
3 and 2
3 and 2
Continuous thermal current I
th
3)
A
63
125
160
250
400
630
800
Rated insulation voltage
U
i
V
690
1000
1000
1000
1000
1000
1000
Rated impulse withstand voltage
U
imp
kV
6
8
8
8
8
8
8
Rated operating voltage
U
e
AC 50 Hz/60 Hz
V
690
DC
V
440 (3 conducting paths series-connected),
220 (2 conducting paths series-connected)
Rated short-circuit making capacity with fuses
2)
at AC 50 Hz/60 Hz 690 V
kA (peak value)
220
220
220
176
176
105
105
Rated conditional short-circuit current with fuses
2)
at AC 50 Hz/60 Hz 690 V
kA (rms value)
100
100
100
80
80
50
50
Max. rated current I
n
of the fuses
A
80
160
160
400
400
630
800
Max. permissible power loss of the installed fuse
NH
W
6
9
11.5
32
45
48
62
BS
W
8 (A2/A3)
11.5 (A4)
11.5
32
45
48
60.5
Permissible let-through current of the fuses
kA
8
17
17
30
4)
30
4)
50
50
Maximum permissible cut-off I
2
t value
kA
2
s
55
223
223
1000
1000
5400
10500
Switching capacity (infeed top or bottom)
at AC 400 V
Breaking current I
c
(p.f.
= 0.35)
A (rms value)
500
1000
1280
2000
3200
5100
6400
Rated operating current I
e
at AC-21A, AC-22A, AC-23A
A
63
125
160
250
400
630
5)
800
5)
Motor switching capacity at AC-23A
kW
30
65
80
132
200
335
400
at AC 500 V
Breaking current I
c
(p.f.
= 0.35)
A (rms value)
500
1000
1280
2000
3200
5100
6400
Rated operating current I
e
at AC-21A, AC-22A, AC-23A
A
63
125
160
250
400
630
5)
630
5)
Motor switching capacity at AC-23A
kW
40
90
110
185
280
425
500
at AC 690 V
Breaking current I
c
(p.f.
= 0.35)
A (rms value)
500
1000
1280
2000
3200
5100
6400
Rated operating current I
e
at AC-21A, AC-22A, AC-23A
A
63
125
160
250
400
630
5)
800
5)
Motor switching capacity at AC-23A
kW
50
110
150
220
375
560
700
at DC 440 V (3 series-connected current path)
Breaking current I
c
(L/R = 15 ms)
A
250
500
640
100
6)
1600
2520
7)
2520
7)
Rated operating current I
e
at DC-23A
A
63
125
160
250
8)
400
630
8)
630
8)
Rated short-time current (1 s current)
kA (rms value)
2.5
3.2
3.2
8
11
32
32
Permissible load
depending on the ambient temperature for open-type instal-
lation in switchboards (e.g. 8NA1) in switchgear cubicles or
switchgear racks at
35 °C
A
63
125
160
250
400
630
800
40 °C
A
63
125
155
250
390
630
780
45 °C
A
63
125
150
250
380
610
760
50 °C
A
63
125
145
250
370
590
740
55 °C
A
63
125
140
240
360
570
720
Permissible ambient temperature
°C
–25 ... +55 for operation
4)
, –50 ... +80 for storage
Mechanical endurance
Operations
15000
15000
15000
12000
12000
3000
3000
Required operating torque
Nm
3
7.5
7.5
16
16
30
30
Degree of protection
IP00/IP20 (from operator side, with fuse and terminal covers)
Power loss of the disconnector at I
th
(plus power loss of the fuses)
W
8.5
22
36
33
86
140
225